BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M321634
Premises: 692 BROADWAY MANHATTAN BIN: 1008529     Block: 531   Lot: 7501
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 692 BROADWAY Census Tract:   55.02 Health Area:  5700
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   GREAT JONES STREET,    EAST 4 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/12/2011 10:02 AM
Application Entered:   12/12/2011 Job Start Date:   12/12/2011
Last Change:   08/22/2025 Job End Date:   06/30/2012
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     08/09/2012      
Field Disp:   N - NO ACCESS
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  

License #: 012106 Licensee Name: LINDA WALSH
Firm: 001504 Firm Name: WALSH ELEC'L CONTR'G, INC
Firm Phone: 718-351-3399  Firm Address: 15 NEWARK AVENUE STATEN ISLAND NY 10302 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
T - TEMPORARY LIGHT & POWER
Total Fee:  $790.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (4  Stores, 20 Apartments)
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:        Z - OTHER (UPGRADE 2000-AMP)                        
Advisory Board Approval # / Submittal #:   50735
Owner / Occup: BRIAN THOMPSON
Owner Business Name: VORNADO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  1  2000-AMPS ; 3-PHASE
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  5  5 SETS 600 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 12/12/2011 Notice: 1 - FIRST NOTICE 06/20/2012
Power Issued: 12/12/2011 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M321634
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/08/2012 06/20/2012 GYM A E (75) (4) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 08/09/2012 08/22/2012 DAH N (30) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW

OBJECTION FOR APPLICATION #: M321634
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: MAIN DISTRIBUTION BLOCK UP,DOORS NOT AS PER DRAWINGTABL. 110.2
OPEN 06/08/2012 06/08/2012
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BSMT: NO GROUNDING TO BUILDING STEEL IS PROVIDED
OPEN 06/08/2012 06/08/2012
 
003 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
A) BSMT: NO GRONDIND ELECTRODE CONDUCTOR PROVIDEDNEW 2000 AMP SERVCE SWS
OPEN 06/08/2012 06/08/2012
 
004 (999) OTHER
FIRE RATED DOORS WITH PANIC HARDWARE NOT PROVIDED FOR NEW 2000A SER-VICE SW #5....... - ART.110.26
OPEN 06/08/2012 06/08/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.