BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M321362
Premises: 317 EAST 34 STREET MANHATTAN BIN: 1021900     Block: 940   Lot: 12
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 317 E 34 ST Census Tract:   78 Health Area:  5000
9TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10016 Community Board:   106
Special Place Name:   DR. MARGIOTTA
DOB Cross Street(s):   QUEENS MIDTOWN TUNNEL APPROACH,    1 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/05/2011 3:27 PM
Application Entered:   12/05/2011 Job Start Date:   12/06/2011
Last Change:   08/22/2025 Job End Date:   03/06/2012
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   BINGEL, LORI       On     07/05/2012      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  

License #: 010676 Licensee Name: JOHN P MAZZA
Firm: 002469 Firm Name: MAZZA ELECTRIC CORP.
Firm Phone: 212-564-0322  Firm Address: 494 8TH AVENUE-6TH FLOOR NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
2 - TEMPORARY CONSTRUCTION
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $140.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: ADAMS & CO. REAL ESTATE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  1 SET 4W #2AWG #6 GROUND
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
009    38  52    16  38     
Buildings Total 38  52    16  38            
Total Units : 153 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 08/09/2012
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M321362
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/05/2012 08/09/2012 LBI A (50) (4) Y
INSPECTION COMMENTS: X

OBJECTION FOR APPLICATION #: M321362
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
9TH FLOOR RECEPTACLES NOT GROUNDED/BONDED AS PER 250.146 (ENTIRE)
OPEN 07/05/2012 07/05/2012
 
002 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
9TH FLOOR #12 WIRES IN 1" EMT (PANEL)
OPEN 07/05/2012 07/05/2012
 
003 (999) OTHER
9TH FLOOR WIRING METHOD (MC CABLE) IN PATIENT CARE AREAS DOES NOT COCOMPLY WITH 517.13 (EXAN AND PROCEDURE ROOMS)
OPEN 07/05/2012 07/05/2012
 
004 (999) OTHER
9TH FLOOR IMPROPER TERMINATION OF EQUIPMENT GROUND CONDUCTERS(PANEL) 250.8 110.14(A)
OPEN 07/05/2012 07/05/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back