BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M320782
Premises: 78 MORTON STREET MANHATTAN BIN: 1010401     Block: 602   Lot: 64
   
Application Completed and Certified

Filed: 78 MORTON ST Census Tract:   69 Health Area:  6400
SIDEWALK SHED Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
Special Place Name:   SIDEWALK
DOB Cross Street(s):   HUDSON STREET,    GREENWICH STREET
Status:   C - JOB IS SIGNED OFF 04/23/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/15/2011 7:28 PM
Application Entered:   11/15/2011 Job Start Date:   11/15/2011
Last Change:   04/23/2013 Job End Date:   11/15/2012
Appointment Status:   
Last Inspection By:   KEMPF, JOHN       On     04/10/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011559 Licensee Name: ALLAN VICTOR
Firm: 003720 Firm Name: RPM ELECTRIC INC
Firm Phone: 212-760-1967  Firm Address: 480 10TH AVENUE NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
W - SIDEWALK SHED WIRING & LIGHTING
Total Fee:  $40.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   SIDEWALK SHED
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: EDMUND KIRSCH
Owner Business Name: PERIMETER BRIDGE & SCAFF
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
SWK                     
Buildings Total                     
Total Units : 4 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/21/2012
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  SIDEWALK SHED LIGHTING FOR PERIMETER SCAFFOLD ONLY

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M320782
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/12/2012 06/21/2012 CCH A (15) (2) Y
INSPECTION COMMENTS: X
 
(2) 04/10/2013 04/18/2013 JKF C R (30) (0) Y
INSPECTION COMMENTS: *NO SHED PRESENT*

OBJECTION FOR APPLICATION #: M320782
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
NO GROUNDING WIRE INSTALLED IN RACEWAY TO FIXTURES
RSLV 06/12/2012 06/12/2012 04/10/2013
 
002 ( 8) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC)
RACEWAY BROKEN
RSLV 06/12/2012 06/12/2012 04/10/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back