BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M320326
Premises: 721 5 AVENUE MANHATTAN BIN: 1035794     Block: 1292   Lot: 7501
  Printable (PDF) version of this Permit  

Filed: 725 FIFTH AV Census Tract:   112.02 Health Area:  4800
APT. #: 47B Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
DOB Cross Street(s):   EAST 56 STREET,    EAST 57 STREET
Status:   P - OBJECTN PENDING AT CONTRACTOR 06/21/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/01/2011 11:00 AM
Application Entered:   11/01/2011 Job Start Date:   11/02/2011
Last Change:   06/21/2012 Job End Date:   07/15/2012
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   TREJO, JORGE       On     06/14/2012      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  

License #: 011516 Licensee Name: DAVID FELLER
Firm: 004053 Firm Name: CBS ELECTRIC INC
Firm Phone: 718-309-1350  Firm Address: 260 MADISON AVE 8TH FLOOR NEW YORK NY 10016 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $56.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: YAQOOB AHMED
Owner Business Name: YA ACQUISITION LLC
Authorized Representative:  DAVID FELLER
Relationship To Owner:   ELECTRICAL CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
047  12    48             
Buildings Total 12    48                
Total Units : 75 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 06/21/2012
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M320326
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/14/2012 06/21/2012 JTE A (55) (5) Y
INSPECTION COMMENTS: X

OBJECTION FOR APPLICATION #: M320326
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
NO AFCI PROVIDED FOR BEDROOMS 210.12 B
OPEN 06/14/2012 06/14/2012
 
002 (999) OTHER
NO DEDICATED CIRCUIT PROVIDED FOR MICROWAVE 210.52 B
OPEN 06/14/2012 06/14/2012
 
003 (999) OTHER
NO GROUND PROVIDED FOR OUTLETS THROUGHOUT 250.146
OPEN 06/14/2012 06/14/2012
 
004 ( 53) GFCI HAS NOT BEEN PROVIDED
NO GFCI PROVIDED IN BATHROOMS BASINS/PLUG-IN TOILET BOWLS 210.8
OPEN 06/14/2012 06/14/2012
 
005 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
PANEL NOT PROVIDED WITH DIRECTORY
OPEN 06/14/2012 06/14/2012