BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M319855
Premises: 140 ORCHARD STREET MANHATTAN BIN: 1005309     Block: 410   Lot: 11
   
Application Completed and Certified

Filed: 140 ORCHARD ST Census Tract:   18 Health Area:  7400
GROUND FLOOR, CORNER STORE Admin Area:   M - MANHATTAN Inspection Area:   V
NEW YORK, NY 10002 Community Board:   103
DOB Cross Street(s):   DELANCEY STREET,    RIVINGTON STREET
Status:   C - JOB IS SIGNED OFF 07/27/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/20/2011 2:26 PM
Application Entered:   10/20/2011 Job Start Date:   10/20/2011
Last Change:   07/27/2012 Job End Date:   10/15/2012
Appointment Status:   
Last Inspection By:   DIMAGGIO, PHILLIP       On     07/09/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  R - REMOVED

License #: 009784 Licensee Name: STANLEY MURRAY
Firm: 000576 Firm Name: GEMINI ELECTRIC CO., INC.
Firm Phone: 718-654-6700  Firm Address: 2460 WILLIAMSBRIDGE ROAD.2ND BRONX NY 10469-4806 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $561.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (3  Stores, 15 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PRATIK SHAH
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  3  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    10  20    12  25         
GND  STORE  80  40    10        45     
Buildings Total 90  60  14       25     45      
Total Units : 236 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 2 + New Meters 1 - Removed Meters 2 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/20/2011 Notice: 1 - FIRST NOTICE 05/18/2012
Power Issued: 10/20/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WE ARE REWIRING COMPLTELEY THE GROCERY/ DELI STORE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M319855
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/04/2012 05/18/2012 GYM V E (65) (11) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 07/09/2012 07/27/2012 PDI C R G (1000) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M319855
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: 2- 200 AMP DISCONNECT SWITCH & 1- 100 AMP DISCONNECT SWITCHBOWDED AFTER SERVICES SWITCH....... - ARTICLE 250.24
RSLV 05/04/2012 05/04/2012 07/09/2012
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
GND FL/BSMT: NO G.F.C.I.PROVIDED FOR BASEMENT SINK AREA,FIRST FLOORKITCHEN AND OUTDOOR CANOPY
RSLV 05/04/2012 05/04/2012 07/09/2012
 
003 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
MAIN FL: ZIP CORD USED FOR ATM MACHINE(PERMANENT WIRING)
RSLV 05/04/2012 05/04/2012 07/09/2012
 
004 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
BSMT: ARMORED CABLE NOT PROPERLY SUPPORTED THRU OUT
RSLV 05/04/2012 05/04/2012 07/09/2012
 
005 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
OUTSIDE: E.M.T.PIPE USED IN FRONT OF STOVE
RSLV 05/04/2012 05/04/2012 07/09/2012
 
006 ( 53) GFCI HAS NOT BEEN PROVIDED
A) BSMT: BATH GROUND FAULT NOT INSTALLED
RSLV 05/04/2012 05/04/2012 07/09/2012
 
007 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
BSMT: WALK-IN BOXES DO NOT HAVE WEATHER PROOF BOXES AND SWITCHES
RSLV 05/04/2012 05/04/2012 07/09/2012
 
008 (999) OTHER
A) BSMT: PANEL USING NEUTRAL BAR AS GROUND........ - ARTICLE 250.24
RSLV 05/04/2012 05/04/2012 07/09/2012
 
009 (999) OTHER
B) BSMT: PHASING AND NEUTRAL NOT GROUPED(BASEMENT PANELS BRANCH CIR-CUIT WIRING)...... - AR 300.20,AR 300.6
RSLV 05/04/2012 05/04/2012 07/09/2012
 
010 (999) OTHER
C) BSMT/1FL: CONTRACTOR CUT-OUT QUICK CONNECT ON FLOURESCENT FIXTUREART.410.73
RSLV 05/04/2012 05/04/2012 07/09/2012
 
011 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
BSMT: KNOCK-OUT MISSING ON 1- 400 AMP SWITCH & 1- 100 DISCONNECT
RSLV 05/04/2012 05/04/2012 07/09/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order