BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
Building Overview Work Items |
QUANTITY |
DESCRIPTION |
SERVICE SWITCHES |
|
A. Up to 100 AMPS |
0 |
|
B. 101 Up to 200 AMPS |
0 |
|
C. 201 Up to 600 AMPS |
1 |
|
D. 601 Up to 1200 AMPS |
0 |
|
E. Over 1200 AMPS |
0 |
|
SER. ENT. & FDR COND (EACH SET) |
|
A. Up to #2 CONDUCTOR |
0 |
|
B. Over #2 to 1/0 |
0 |
|
C. Over 1/0 to 250 MCM |
3 |
|
D. Over 250 MCM |
1 |
|
PANELS |
|
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
C. 3 Phase Up to 225 AMPS |
3 |
|
D. 3 Phase Over 225 AMPS |
0 |
|
ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
B. Each Additional 10 Floors Or Less |
0 |
|
BOILER CONTROLS |
0 |
|
OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
|
001 |
(999) |
OTHER BSMT: 2- 200 AMP DISCONNECT SWITCH & 1- 100 AMP DISCONNECT SWITCHBOWDED AFTER SERVICES SWITCH....... - ARTICLE 250.24 |
RSLV |
05/04/2012 |
05/04/2012 |
07/09/2012 |
|
002 |
( 53) |
GFCI HAS NOT BEEN PROVIDED GND FL/BSMT: NO G.F.C.I.PROVIDED FOR BASEMENT SINK AREA,FIRST FLOORKITCHEN AND OUTDOOR CANOPY |
RSLV |
05/04/2012 |
05/04/2012 |
07/09/2012 |
|
003 |
( 15) |
FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD MAIN FL: ZIP CORD USED FOR ATM MACHINE(PERMANENT WIRING) |
RSLV |
05/04/2012 |
05/04/2012 |
07/09/2012 |
|
004 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED BSMT: ARMORED CABLE NOT PROPERLY SUPPORTED THRU OUT |
RSLV |
05/04/2012 |
05/04/2012 |
07/09/2012 |
|
005 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED OUTSIDE: E.M.T.PIPE USED IN FRONT OF STOVE |
RSLV |
05/04/2012 |
05/04/2012 |
07/09/2012 |
|
006 |
( 53) |
GFCI HAS NOT BEEN PROVIDED A) BSMT: BATH GROUND FAULT NOT INSTALLED |
RSLV |
05/04/2012 |
05/04/2012 |
07/09/2012 |
|
007 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED BSMT: WALK-IN BOXES DO NOT HAVE WEATHER PROOF BOXES AND SWITCHES |
RSLV |
05/04/2012 |
05/04/2012 |
07/09/2012 |
|
008 |
(999) |
OTHER A) BSMT: PANEL USING NEUTRAL BAR AS GROUND........ - ARTICLE 250.24 |
RSLV |
05/04/2012 |
05/04/2012 |
07/09/2012 |
|
009 |
(999) |
OTHER B) BSMT: PHASING AND NEUTRAL NOT GROUPED(BASEMENT PANELS BRANCH CIR-CUIT WIRING)...... - AR 300.20,AR 300.6 |
RSLV |
05/04/2012 |
05/04/2012 |
07/09/2012 |
|
010 |
(999) |
OTHER C) BSMT/1FL: CONTRACTOR CUT-OUT QUICK CONNECT ON FLOURESCENT FIXTUREART.410.73 |
RSLV |
05/04/2012 |
05/04/2012 |
07/09/2012 |
|
011 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX BSMT: KNOCK-OUT MISSING ON 1- 400 AMP SWITCH & 1- 100 DISCONNECT |
RSLV |
05/04/2012 |
05/04/2012 |
07/09/2012 |