| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
30A FIRE ALARM |
| B. 101 Up to 200 AMPS |
1 |
200A RETAIL #2 |
| C. 201 Up to 600 AMPS |
1 |
400A RETAIL #1 |
| D. 601 Up to 1200 AMPS |
2 |
800A MDP & 800A APT, |
| E. Over 1200 AMPS |
1 |
1200A FIRE PUMP |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
#10 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
2 |
1-3/0 & 1-4/0 |
| D. Over 250 MCM |
5 |
3-500KCMIL & 2-350KCMIL |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
14 |
APARTMENTS |
| C. 3 Phase Up to 225 AMPS |
7 |
HOUSE/RETAILS |
| D. 3 Phase Over 225 AMPS |
1 |
MDP-1 |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER BSMT: GROUNDING ELECTRODE CONDUCTOR IS NOT PROVIDED IN EACK SERVICESW. 250.64 |
RSLV |
10/18/2013 |
10/18/2013 |
11/25/2013 |
| |
| 002 |
(999) |
OTHER A) ALL FL: ARC FLASH WARNING LABELS ARE NOT PROVIDED. 110.16 |
RSLV |
10/18/2013 |
10/18/2013 |
11/25/2013 |
| |
| 003 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE 1ST FL: NEW PANEL 255 AMP FUSES AT 400 AMP |
RSLV |
10/18/2013 |
10/18/2013 |
11/25/2013 |
| |
| 004 |
(999) |
OTHER B) BSMT: NO PANIC HARDWARE PROVIDED DOOR NEW 1200 AMP. 110.26 |
RSLV |
10/18/2013 |
10/18/2013 |
11/25/2013 |
| |
| 005 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED BSMT,1,2FL: BSMT BOILER ROOM 1,2 FLOOR COMMERCIAL AREA |
RSLV |
10/18/2013 |
10/18/2013 |
11/25/2013 |
| |
| 006 |
(999) |
OTHER C) ALL FLS: ARC FLASH WARNING LABELS ARE NOT PROVIDED. 110.16 |
RSLV |
10/18/2013 |
10/18/2013 |
11/25/2013 |
| |
| 007 |
(999) |
OTHER D) 1ST FL: OUTLET IS NOT PROVIDED TO SERVICE A/C OR HEATING UNITS210.63 |
RSLV |
10/18/2013 |
10/18/2013 |
11/25/2013 |
| |
| 008 |
( 50) |
TEMPORARY OPEN WIRING IN CONTACT WITH PARTS OF THE BUILDING 1,2FLS: COMMERCIAL SPACE |
RSLV |
10/18/2013 |
10/18/2013 |
11/25/2013 |
| |
| 009 |
( 49) |
TEMPORARY OPEN WIRING INSTALLED IS NOT PROPERLY SUPPORTED 1,2FLS: COMMERCIAL SPACE |
RSLV |
10/18/2013 |
10/18/2013 |
11/25/2013 |
| |
| 010 |
( 45) |
FIXTURE NOT INSTALLED IN AN APPROVED MANNER 1,2FLS: COMMERCIAL SPACE |
RSLV |
10/18/2013 |
10/18/2013 |
11/25/2013 |
| |
| 011 |
(999) |
OTHER ALL FLS: OUTLET BOXES NOT ALL ARE BONDED. 250.146 |
RSLV |
10/18/2013 |
10/18/2013 |
11/25/2013 |