| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
1 |
|
| B. Each Additional 10 Floors Or Less |
1 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH ROOF ALL ELEVATOR DISCONNECT SWITCHES; NEUTRAL BONDED 250.24A |
RSLV |
03/14/2013 |
03/14/2013 |
08/13/2013 |
| |
| 002 |
(999) |
OTHER ROOF 1F10304 DOUBLE LUG NO POWER 110.14 A,3,B |
RSLV |
03/14/2013 |
03/14/2013 |
08/13/2013 |
| |
| 003 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE ROOF 1P45839, 1P4T838 DISC SWITCH; BUGHING MISSING 300.4 11 |
RSLV |
03/14/2013 |
03/14/2013 |
08/13/2013 |
| |
| 004 |
( 33) |
KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX ROOF SWITCH GFCI; K/O MISSING 110.12A |
RSLV |
03/14/2013 |
03/14/2013 |
08/13/2013 |
| |
| 005 |
(999) |
OTHER ROOF IF10304 CONTROL BOX; LB ON TOP, NO ACCESS 110 |
RSLV |
03/14/2013 |
03/14/2013 |
08/13/2013 |
| |
| 006 |
(999) |
OTHER ROOF DOUBLE LUG ON GROUND IN CONTROL BOX 110.14 A, 3B |
RSLV |
03/14/2013 |
03/14/2013 |
08/13/2013 |
| |
| 007 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED ROOF 1P45835 CDD CONNECTOR NOT APPROVED 110.2 314.25 |
RSLV |
03/14/2013 |
03/14/2013 |
08/13/2013 |
| |
| 008 |
( 29) |
OUTLET BOXES ARE NOT COVERED ROOF GFCI NO COKER BY CONTROL BOX OF 1P45838 314.25 |
RSLV |
03/14/2013 |
03/14/2013 |
08/13/2013 |
| |
| 009 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED ROOF ALL ELEVATOR MOTOR LOOSE EQUIPMENT GROUND 250.4 |
RSLV |
03/14/2013 |
03/14/2013 |
08/13/2013 |
| |
| 010 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED ROOF PANEL 2P CB MISSING HANDLE TIE |
RSLV |
03/14/2013 |
03/14/2013 |
08/13/2013 |
| |
| 011 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH ROOF PANEL IN ELEVATOR ROOM; NEUTRAL BONDED A/C CKT 250.24 A |
RSLV |
03/14/2013 |
03/14/2013 |
08/13/2013 |
| |
| 012 |
( 19) |
DEFECTIVE WIRING IS IN USE (ALL FLOORS)1F10304 TOP OF CAR; DEFECTIVE GFCI WIRING (OPEN GROUND) 110.2A |
RSLV |
03/14/2013 |
08/13/2013 |
06/17/2020 |
| |
| 013 |
(178) |
THERE IS NO LIGHT IN THE ELEVATOR PIT (ALL FLOORS) 1F10304 PIT NO LIGHT |
RSLV |
03/14/2013 |
08/13/2013 |
06/17/2020 |
| |
| 014 |
( 18) |
DEFECTIVE RECEPTACLES ARE IN USE 1F10304 PIT; DEFECTIVE GFCI 110.2A |
RSLV |
03/14/2013 |
03/14/2013 |
08/13/2013 |
| |
| 015 |
(999) |
OTHER 1F10304 UNDER CAR NO ACCESS |
RSLV |
03/14/2013 |
03/14/2013 |
08/13/2013 |
| |
| 016 |
(211) |
RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED (ALL FLOORS)AT EMR, PIT, 250.146, RECEPTACLE INSTALL ARE NOT GROUNDED TO BOXE |
RSLV |
07/24/2019 |
07/24/2019 |
06/17/2020 |
| |
| 017 |
(999) |
OTHER (ALL FLOORS) ELEVATOR PIT, 620.24(A,B), NO LIGHT IN ELEVATOR. |
RSLV |
07/24/2019 |
07/24/2019 |
06/17/2020 |
| |
| 018 |
(999) |
OTHER (ALL FLOORS)EMR, 110.16 ARC FLASH LABEL NOT PROVIDED / INSTALL AT ELECTRICALEQUIPMENT. |
RSLV |
07/24/2019 |
07/24/2019 |
06/17/2020 |
| |
| 019 |
(999) |
OTHER (ALL FLOORS)110.21/22, IDENTIFICATION OF ELEVATOR DIS SW FEEDER, NOTINDENTIFIED. |
RSLV |
07/24/2019 |
07/24/2019 |
06/17/2020 |
| |
| 020 |
( 18) |
DEFECTIVE RECEPTACLES ARE IN USE (ROOF) AT EMR,110.2(A), RECEPTACLE INSTALL ARE DEFECTIVE. |
RSLV |
07/24/2019 |
07/24/2019 |
06/17/2020 |
| |
| 021 |
(212) |
NO GROUND PROVIDED FOR SEPARATELY DERIVED SYSTEM (ROOF)250.30, TRANSFORMER/ ELEVATOR VOLTAGE STABILIZER, NOT BOND TO STEEL/BUILDING STRUCTURE. |
RSLV |
07/24/2019 |
07/24/2019 |
06/17/2020 |
| |
| 022 |
(220) |
DOUBLE LUGGING IN SERVICE SWITCH (ROOF)ALL ELECTRICAL EQUIPMENT, 110.14(A), MULTIPLE CONDUCTOR INSTALL ATSINGLE LUGS. |
RSLV |
07/24/2019 |
07/24/2019 |
06/17/2020 |
| |
| 023 |
(302) |
ELEVATOR MOTORS/CONTROLLERS/ENCLOSURES NOT GROUNDED (ROOF)AT EMR, ALL, 620.82, ELEVATOR CONTROLLER NOT BOND TO EQUIPMENT,THRU-OUT. |
RSLV |
07/24/2019 |
07/24/2019 |
06/17/2020 |
| |
| 024 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (ROOF) 358.30, EMT CONDUIT NOT SUPPORTED. |
RSLV |
07/24/2019 |
07/24/2019 |
06/17/2020 |
| |
| 025 |
(999) |
OTHER (ROOF) EMR, ALL, AM 600.7, ELEVATOR CAR LIGHT DIS SW, CONDUCTOR IMPROPERSIZE, 14 AWG USED. |
RSLV |
07/24/2019 |
07/24/2019 |
06/17/2020 |
| |
| 026 |
(999) |
OTHER (ROOF) 250.110, EQUIPMENT BONDING, CAR LIGHT DIS SW, NOT GROUNDED,THRU-OUT. |
RSLV |
07/24/2019 |
07/24/2019 |
06/17/2020 |
| |
| 027 |
(999) |
OTHER (ROOF) 348.60, FMC BONDING REQUIRE AT MOTOR, THRU-OUT. |
RSLV |
07/24/2019 |
07/24/2019 |
06/17/2020 |