| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
3 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
2 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER BSMT: TAP CONDUCTOR UNDER SIZED 4000 FUSE,3/4 TAP MADE FOR 1ST FLOOR OF RESTAURANT....... - 240.21(B)(1)4) |
RSLV |
03/18/2012 |
03/18/2012 |
06/30/2012 |
| |
| 002 |
(999) |
OTHER A) 200AMP DISC SW FOR 1ST FLOOR NEUTRAL BONDED AFTER SVC SW... -250.24(A)(5) |
RSLV |
03/18/2012 |
03/18/2012 |
06/30/2012 |
| |
| 003 |
(999) |
OTHER BSMT NEW 400AMP DISC SW NEUTRAL BAR BONDED AFTER SERVICE SWART. 250-24 |
RSLV |
06/30/2012 |
06/30/2012 |
08/27/2012 |
| |
| 004 |
( 4) |
SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL BSMT 400AMP DISC SW (1) SET 500MCM ADVISORY BOARD CALENDAR NUMBERCONTRACTOR TAP OFF LOADSIDE OF 4000AMP SERVICE SW |
RSLV |
06/30/2012 |
06/30/2012 |
08/27/2012 |
| |
| 005 |
( 4) |
SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL SW GEAR 110.2 SERV IN EXCESS OF 1000KV HAS NOT BEEN SUBMITTED FORAPPROVAL |
RSLV |
08/27/2012 |
08/27/2012 |
09/12/2012 |
| |
| 006 |
(999) |
OTHER SW GEAR NEW 400AMP DISC SW NEUTRAL BAR BONDED AFTER SERV SW 250.24 |
RSLV |
08/27/2012 |
08/27/2012 |
09/12/2012 |
| |
| 007 |
( 6) |
FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION CELLAR: CONTRACTOR NEEDS LOAD CALCULATION TO SHOW THAT THE 600ASWITCH CAN SUPPORT HIS 400A SWITCH AND THE EXISTING ONE.... - 215.5 |
RSLV |
09/12/2012 |
09/12/2012 |
12/07/2012 |