BIS Menu  |  Applications  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M318402
Premises: 29 WEST 35 STREET MANHATTAN BIN: 1015891     Block: 837   Lot: 23
   
Application Completed and Certified

Filed: 29 W 35 ST Census Tract:   84 Health Area:  5200
CELLAR, 1ST FLOOR Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   105
DOB Cross Street(s):    5 AVENUE,    AVENUE OF THE AMERICAS
Status:   C - JOB IS SIGNED OFF 12/19/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/03/2011 9:15 AM
Application Entered:   09/03/2011 Job Start Date:   09/03/2011
Last Change:   12/19/2012 Job End Date:   12/30/2011
Appointment Status:   
Last Inspection By:   KAFFETZAKIS, MICHAIL       On     12/07/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011777 Licensee Name: ON GUK TSE
Firm: 003385 Firm Name: HI-RITE ELECTRIC CORP
Firm Phone: 718-680-2688  Firm Address: 6508 6TH AVENUE BROOKLYN NY 11220 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $336.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RON MOVA
Owner Business Name: AMERICAN STATE EQUITIES
Authorized Representative:  RON MOVA
Relationship To Owner:   PARTNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  3  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    20  30    10  20         
001    50  30    15  50  22         
Buildings Total 70  60    25  70     31           
Total Units : 256 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 09/21/2012
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  THIS JOB IS TO USE NYC 2007 ELECTRICAL CODE.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M318402
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/18/2012 03/27/2012 JSB A (60) (2) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 06/30/2012 07/26/2012 GYM A R (65) (2) Y
INSPECTION COMMENTS: X
 
(3) 08/27/2012 08/31/2012 RFY A Y (40) (2) Y
INSPECTION COMMENTS: NONE
 
(4) 09/12/2012 09/21/2012 IOS A Y (45) (1) Y
INSPECTION COMMENTS: *THE CONTRACTOR IS NOT TAPPING OFF @ 400A SWITCH AND IS NOW TAPPING OFF A 600A SWITCH WHICH IS AFTER THE 4000A SWITCH,THE 600A SWITCH HAS A SET OF 500 MCM ALREADY*........ - SEE VIOLATION DETAILS
 
(5) 12/07/2012 12/19/2012 MFF C R (40) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M318402
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: TAP CONDUCTOR UNDER SIZED 4000 FUSE,3/4 TAP MADE FOR 1ST FLOOR OF RESTAURANT....... - 240.21(B)(1)4)
RSLV 03/18/2012 03/18/2012 06/30/2012
 
002 (999) OTHER
A) 200AMP DISC SW FOR 1ST FLOOR NEUTRAL BONDED AFTER SVC SW... -250.24(A)(5)
RSLV 03/18/2012 03/18/2012 06/30/2012
 
003 (999) OTHER
BSMT NEW 400AMP DISC SW NEUTRAL BAR BONDED AFTER SERVICE SWART. 250-24
RSLV 06/30/2012 06/30/2012 08/27/2012
 
004 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
BSMT 400AMP DISC SW (1) SET 500MCM ADVISORY BOARD CALENDAR NUMBERCONTRACTOR TAP OFF LOADSIDE OF 4000AMP SERVICE SW
RSLV 06/30/2012 06/30/2012 08/27/2012
 
005 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
SW GEAR 110.2 SERV IN EXCESS OF 1000KV HAS NOT BEEN SUBMITTED FORAPPROVAL
RSLV 08/27/2012 08/27/2012 09/12/2012
 
006 (999) OTHER
SW GEAR NEW 400AMP DISC SW NEUTRAL BAR BONDED AFTER SERV SW 250.24
RSLV 08/27/2012 08/27/2012 09/12/2012
 
007 ( 6) FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION
CELLAR: CONTRACTOR NEEDS LOAD CALCULATION TO SHOW THAT THE 600ASWITCH CAN SUPPORT HIS 400A SWITCH AND THE EXISTING ONE.... - 215.5
RSLV 09/12/2012 09/12/2012 12/07/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back