BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M318374
Premises: 281 BROADWAY MANHATTAN BIN: 1087951     Block: 149   Lot: 31
   
Application Completed and Certified

Filed: 281 BROADWAY Census Tract:   21 Health Area:  7700
BASE &1ST FLOOR Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10007 Community Board:   101
Special Place Name:   READ STREET
DOB Cross Street(s):   CHAMBERS STREET,    READE STREET
Status:   C - JOB IS SIGNED OFF 02/28/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/02/2011 10:00 AM
Application Entered:   09/02/2011 Job Start Date:   09/02/2011
Last Change:   02/28/2013 Job End Date:   03/01/2012
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     02/21/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010347 Licensee Name: HOWARD BRAUNSTEIN
Firm: 000153 Firm Name: ARCH ELECTRIC, INC.
Firm Phone: 718-529-9100  Firm Address: 23-82 BQE WEST #202 ASTORIA NY 11103 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $190.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LESLIE FELDMAN
Owner Business Name: 281 BROADWAY ASSOCIATES
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  4 # 600 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/02/2011 Notice: 1 - FIRST NOTICE 07/30/2012
Power Issued: 09/02/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  SERVICE WORK FOR CHIPOTLE MEXICAN GRILL

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M318374
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/09/2012 07/30/2012 GYM V E (95) (3) Y
INSPECTION COMMENTS: N/A
 
(2) 12/27/2012 01/10/2013 DAH Z (0) (0) Y
INSPECTION COMMENTS: NONE
 
(3) 02/21/2013 02/28/2013 GYM C R E (50) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M318374
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT; ART 110.2 ELECTRICAL SERVICE ROOM LAYOUT IS NOT AS PER DRAWING(2) 400AMP TRANS'S DISC. SWPS 1 NEW C-H 200AMP DISC. SW CAL#51118
RSLV 07/09/2012 07/09/2012 02/21/2013
 
002 (999) OTHER
BSMT; ART 110.2 3-500 MCM CU/PH N IN 3-3 1/2" C CU/PH 1 N IN 1-4"CIS NOT AS PER DRAWING CAL # 51118 REY O
RSLV 07/09/2012 07/09/2012 02/21/2013
 
003 (999) OTHER
BSMT; (1) 600 MCM CU/PH AND NEUTRAL EQUIPMENT GROUPING IS NOT AS PERTABLE 250.122
RSLV 07/09/2012 07/09/2012 02/21/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order