| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
|
| C. 201 Up to 600 AMPS |
2 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
|
| D. Over 250 MCM |
2 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
|
| D. 3 Phase Over 225 AMPS |
2 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
1 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED (ALL FLOORS) GROUND BAR NOT BONDED IN SOME PANELS. |
RSLV |
12/15/2017 |
12/15/2017 |
01/09/2019 |
| |
| 002 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (ALL FLOORS) PANELS NOT PROPERLY LABELED |
RSLV |
12/15/2017 |
12/15/2017 |
01/09/2019 |
| |
| 003 |
(999) |
OTHER (ALL FLOORS) ARC FLASH STICKER NEEDED ON ALL EQUIPMENTS. 110.16 |
RSLV |
12/15/2017 |
12/15/2017 |
03/22/2018 |
| |
| 004 |
(999) |
OTHER (ALL FLOORS) BREAKER TIES NEEDED ON SHARED NEUTRALS. 210.4 |
RSLV |
12/15/2017 |
12/15/2017 |
03/22/2018 |
| |
| 005 |
(124) |
TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE (BASEMENT) # 14 CORD TAP TO #4 IN KITCHEN FOR MIXER. |
RSLV |
12/15/2017 |
12/15/2017 |
06/05/2019 |
| |
| 006 |
(126) |
BASEMENT WATER MAIN GROUND NOT INSTALLED ON WATER MAIN (BASEMENT) NO WATER MAIN GROUND PROVIDED. |
RSLV |
12/15/2017 |
12/15/2017 |
03/22/2018 |
| |
| 007 |
(133) |
NO GROUND ROD: BASEMENT OR OUTSIDE (BASEMENT) NO SUPPLEMENTAL GROUND ON SERVICE. |
RSLV |
12/15/2017 |
12/15/2017 |
01/09/2019 |
| |
| 008 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED (BASEMENT) BX HANGING AT HOOD IN KITCHEN |
RSLV |
12/15/2017 |
12/15/2017 |
01/09/2019 |
| |
| 009 |
(260) |
SIGNAGE NOT PROVIDED FOR SERVICE ROOM (BASEMENT) NO SIGNAGE ON CLOSET DOOR. |
RSLV |
12/15/2017 |
12/15/2017 |
01/09/2019 |
| |
| 010 |
(272) |
EQUIPMENT GROUNDING CONDUCTOR NOT PROPERLY INSTALLED (BASEMENT) EQUIPMENT GROUND CONNECT TO NEUTRAL BAR |
RSLV |
12/15/2017 |
12/15/2017 |
01/09/2019 |
| |
| 011 |
(999) |
OTHER (BASEMENT) NOT SUFFICIENT LIGHTING IN SERVICE AREA. |
RSLV |
12/15/2017 |
12/15/2017 |
03/22/2018 |
| |
| 012 |
(111) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED (FLOOR: 002) NO WORKING SPACE FOR 2 FL PANEL |
RSLV |
03/22/2018 |
03/22/2018 |
01/09/2019 |
| |
| 013 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (FLOOR: 002) SHEET ROCK SCREWS USED FORD DIMMER 2 FL 110.3 |
RSLV |
03/22/2018 |
03/22/2018 |
01/09/2019 |
| |
| 014 |
(999) |
OTHER (ALL FLOORS) NO DISCONNECTS ON MOTORS OVER 1/8 HP 430 |
RSLV |
03/22/2018 |
03/22/2018 |
01/09/2019 |
| |
| 015 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (BASEMENT) ALL SERVICE ENTRANCE TROUGH AND PANEL NOT BONDED 250.92 |
RSLV |
03/22/2018 |
03/22/2018 |
01/09/2019 |
| |
| 016 |
(111) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED (BASEMENT) NO 90 SWING ON ALL EL PANELS CLOSET 110.26 |
RSLV |
03/22/2018 |
03/22/2018 |
01/09/2019 |
| |
| 017 |
(136) |
GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS (BASEMENT) BOTH SIDES OF GEC 250.64 |
RSLV |
03/22/2018 |
03/22/2018 |
01/09/2019 |
| |
| 018 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (BASEMENT) NO BOND FOR MC CABLE T OUT 250.148 |
RSLV |
03/22/2018 |
03/22/2018 |
06/05/2019 |
| |
| 019 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (BASEMENT) GROUND AND NEURTAL NOT TOGETHER IN ALL SERVICE SW 250.24 |
RSLV |
03/22/2018 |
03/22/2018 |
06/05/2019 |
| |
| 020 |
(286) |
NO GFCI IN COMMERCIAL KITCHEN (BASEMENT) NOT ALL 120V CKTS PROTECTED 210.8 |
RSLV |
03/22/2018 |
03/22/2018 |
06/05/2019 |
| |
| 021 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (BASEMENT) 600 AMP PANEL AND 6O AMP DISCONNECT |
RSLV |
03/22/2018 |
03/22/2018 |
01/09/2019 |
| |
| 022 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (BASEMENT) BX SLEEVED THRU PIPE IN VAULT |
RSLV |
03/22/2018 |
03/22/2018 |
06/05/2019 |
| |
| 023 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (BASEMENT) OPEN LUG ON COLLECTOR BAR UNDER SIZED 250.64 110.3 |
RSLV |
03/22/2018 |
03/22/2018 |
01/09/2019 |
| |
| 024 |
(999) |
OTHER (BASEMENT) BX DOES NOT ENTER CONNECTOR LIGHT IN CLOSET 300.10 |
RSLV |
03/22/2018 |
03/22/2018 |
01/09/2019 |
| |
| 025 |
(999) |
OTHER (BASEMENT) 60 AMP DISHWASHER DISCONNECT USED AS RACEWAY 312 |
RSLV |
03/22/2018 |
03/22/2018 |
01/09/2019 |
| |
| 026 |
(999) |
OTHER (BASEMENT)TROUGH/BOX UNDER SIZED FOR BOTH SERVICE ENTRANCE 376.22 314.16 |
RSLV |
03/22/2018 |
03/22/2018 |
01/09/2019 |
| |
| 027 |
( 29) |
OUTLET BOXES ARE NOT COVERED (BASEMENT) MISSING COVERS 314.25 |
RSLV |
01/09/2019 |
01/09/2019 |
06/05/2019 |
| |
| 028 |
(999) |
OTHER (BASEMENT) ARC FLASH LABEL NOT PROVIDED110 16 T-OUT |
RSLV |
01/09/2019 |
01/09/2019 |
06/05/2019 |