Electrical Application Details for App #: M317478
Premises: 1589 1 AVENUE MANHATTAN BIN: 1049893     Block: 1545   Lot: 30
   
Application Completed and Certified

Filed: 1593 FIRST AV Census Tract:   138 Health Area:  3700
RESTAURANT Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10028 Community Board:   108
DOB Cross Street(s):   EAST 82 STREET,    EAST 83 STREET
Status:   C - JOB IS SIGNED OFF 07/05/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/09/2011 9:08 AM
Application Entered:   08/09/2011 Job Start Date:   08/10/2011
Last Change:   07/05/2012 Job End Date:   06/30/2012
Appointment Status:   
Last Inspection By:   DORSAINVILLE, R       On     06/21/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010891 Licensee Name: DARIO KNESICH
Firm: 004084 Firm Name: GLENDALE ELECTL CONTNG IN
Firm Phone: 718-772-4544  Firm Address: 58-80 56TH STREET MASPETH NY 11378 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $76.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ALVIN GLICK
Owner Business Name: MAUTNER/GLICK CORP
Authorized Representative:  ALVIN GLICK
Relationship To Owner:   MANAGING AGENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    42  48    21  42         
Buildings Total 42  48    21  42              
Total Units : 157 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/01/2012
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M317478
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/22/2011 01/09/2012 CCH A (90) (6) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 05/16/2012 06/01/2012 GYM A R (50) (1) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(3) 06/21/2012 07/05/2012 RID C R (60) (0) Y
INSPECTION COMMENTS: X

OBJECTION FOR APPLICATION #: M317478
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
OUTLET NOT BONDED TO BOX........ - 250.146
RSLV 12/22/2011 12/22/2011 05/16/2012
 
002 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
BASEMENT: WALL LIGHT WITH PLUG NEED OUTLET
RSLV 12/22/2011 12/22/2011 05/16/2012
 
003 ( 37) MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED
BASEMENT: WALK-IN FRIDGE NO DIS ON FAN
RSLV 12/22/2011 12/22/2011 05/16/2012
 
004 ( 53) GFCI HAS NOT BEEN PROVIDED
BASEMENT: OUTBLET NOT G.F.C.I.ON WALL
RSLV 12/22/2011 12/22/2011 05/16/2012
 
005 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
BASEMENT: EXPOSE WIRE IN CEILING
RSLV 12/22/2011 12/22/2011 05/16/2012
 
006 (999) OTHER
M.C.CABLE OUTLET BOXES NOT BONDED........ - 250.146
RSLV 12/22/2011 12/22/2011 05/16/2012
 
007 ( 28) ELECTRICAL MATERIAL USED FOR LUMINAIRES HAS NOT BEEN APPROVED
1ST FL: CEILING CHAIN HUNG FIXTURE NOT U.L.LISTEDWAITING FOR INFO FROM CONTRACTOR ON FIXTURE CERTIFICATION
RSLV 05/16/2012 05/16/2012 06/21/2012