BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M316659
Premises: 626 5 AVENUE MANHATTAN BIN: 1083860     Block: 1266   Lot: 1
  Printable (PDF) version of this Permit  

Filed: 630 5 AV Census Tract:   104 Health Area:  4800
25TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10020 Community Board:   105
Special Place Name:   28846/GANNON
DOB Cross Street(s):   EAST 50 STREET,    EAST 51 STREET
Status:   P - OBJECTN PENDING AT CONTRACTOR 08/15/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/15/2011 1:01 PM
Application Entered:   07/15/2011 Job Start Date:   07/15/2011
Last Change:   08/15/2012 Job End Date:   09/15/2011
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   TREJO, JORGE       On     07/31/2012      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  

License #: 011809 Licensee Name: ARTHUR GROSSMAN
Firm: 000176 Firm Name: ATLAS-ACON ELEC. SERVICE
Firm Phone: 212-741-0600  Firm Address: 283 HUDSON STREET NEW YORK NY 10013 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $187.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: RCPI LANDMARK PROPERTIES
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  100 AMP 42 CKT
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
025      59    32  108             
Buildings Total   59    32  108                
Total Units : 199 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 08/15/2012
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M316659
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/31/2012 08/15/2012 JTE A (50) (2) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M316659
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 11) FEEDER CONDUCTORS ARE NOT OF PROPER SIZE
25TH FL,FEEDER CODUCTORS ARE NOT OF PROPER SIZE,600AMP DISCONNECT SWITCH FUSED AT 40AMP WITH #6 AWG, THHN FEEDING 100AMP MAIN BK PNL
OPEN 07/31/2012 07/31/2012
 
002 (999) OTHER
2ND FL, DOUBLE LUGGING AT 600AMP DISCONNECT SWITCH IN ELECTRIC CLOSET ART 110.14 (A)
OPEN 07/31/2012 07/31/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order