BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M315986
Premises: 88 WEST WASHINGTON PLACE MANHATTAN BIN: 1008869     Block: 552   Lot: 7504
   
Application Completed and Certified

Filed: 88 WASHINGTON PL Census Tract:   65 Health Area:  5700
WASHINGTON PLACE Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):   WASHINGTON SQUARE WEST,    AVENUE OF THE AMERICAS
Status:   C - JOB IS SIGNED OFF 05/11/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/24/2011 2:26 PM
Application Entered:   06/24/2011 Job Start Date:   06/30/2011
Last Change:   05/11/2012 Job End Date:   11/30/2011
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     04/21/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010808 Licensee Name: GEORGE ANASTASAKIS
Firm: 003482 Firm Name: METROPOLIS ELECTRIC CORP
Firm Phone: 718-205-7605  Firm Address: 110 WEST 40 STREET SUITE 600 NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $79.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   DAY CARE CENTER
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: MANHATTAN KIDS CLUB
Authorized Representative:  ANTHONY MELLIS
Relationship To Owner:   ELECTRICIAN


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002      42  15  15  95             
Buildings Total   42  15  15  95                
Total Units : 167 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/13/2012
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M315986
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/03/2012 03/13/2012 GYM A (80) (5) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 04/21/2012 05/01/2012 DAH C R (40) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M315986
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
2FL: ALL AREA WITH MC CABLE BRANCH CIRCUIT WIRING OUTLET BOXES ARENOT BONDED.......... - ART.250.146 148
RSLV 03/03/2012 03/03/2012 04/21/2012
 
002 ( 49) TEMPORARY OPEN WIRING INSTALLED IS NOT PROPERLY SUPPORTED
2FL: CEILING
RSLV 03/03/2012 03/03/2012 04/21/2012
 
003 ( 50) TEMPORARY OPEN WIRING IN CONTACT WITH PARTS OF THE BUILDING
2FL: CEILING
RSLV 03/03/2012 03/03/2012 04/21/2012
 
004 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
2FL: 250 AMP PANELS TRIM BREAK ROOM
RSLV 03/03/2012 03/03/2012 04/21/2012
 
005 (999) OTHER
2FL: PANTRY ELECTRIC RANGE WITH COIL COOK TOP NEUTRAL BAR BONDEDAFTER S.S........ - 250.24
RSLV 03/03/2012 03/03/2012 04/21/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.