BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M315847
Premises: 220 WEST 16 STREET MANHATTAN BIN: 1013780     Block: 765   Lot: 55
   
Application Completed and Certified

Filed: 220 W 16 ST Census Tract:   81 Health Area:  5600
8 APTS. 2 APTS ON EACH FL Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10011 Community Board:   104
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   C - JOB IS SIGNED OFF 12/14/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/21/2011 10:19 PM
Application Entered:   06/21/2011 Job Start Date:   06/24/2011
Last Change:   12/14/2012 Job End Date:   08/16/2011
Appointment Status:   
Last Inspection By:   JEFFERSON, CHARLES       On     06/26/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009952 Licensee Name: JOHN F ISOLANO
Firm: 002705 Firm Name: JFI ELECTRIC CO.
Firm Phone: 718-641-2447  Firm Address: 24-25 46TH STREET L.I.C. NY 11103 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
2 - TEMPORARY CONSTRUCTION
6 - GENERAL WIRING
Total Fee:  $430.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BRAD LENT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  200 3/PHASE
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  8  6THNN
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  4/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  8  1/PHASE 100AMP.
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 9 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/21/2011 Notice: 1 - FIRST NOTICE 01/17/2012
Power Issued: 06/21/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M315847
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/03/2012 01/17/2012 CCH A G (60) (5) Y
INSPECTION COMMENTS: *ONLY 1 APARTMENT PANEL INSTALLED - APT.41* SEE VIOLATION DETAILS
 
(2) 06/26/2012 07/17/2012 CJE C R E (30) (0) Y
INSPECTION COMMENTS: X

OBJECTION FOR APPLICATION #: M315847
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
BASEMENT: OLD SER NOT DISCONNECTED AND REMOVED
RSLV 01/03/2012 01/03/2012 06/26/2012
 
002 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
BASEMENT: OLD FEEDERS #10 ON 60 AMP BREAKER
RSLV 01/03/2012 01/03/2012 06/26/2012
 
003 (999) OTHER
BASEMENT: NO SUPP GROUND....... - 250.53.D(2)
RSLV 01/03/2012 01/03/2012 06/26/2012
 
004 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BASEMENT: E.M.T.NOT BONDED TO 200A SER SWITCH
RSLV 01/03/2012 01/03/2012 06/26/2012
 
005 (999) OTHER
BASEMENT: NEED LIGHT OVER NEW SERVICE........ - 110.26.D
RSLV 01/03/2012 01/03/2012 06/26/2012