Electrical Application Details for App #: M315441
Premises: 78 MORTON STREET MANHATTAN BIN: 1010401     Block: 602   Lot: 64
   
Application Completed and Certified

Filed: 78 MORTON ST Census Tract:   69 Health Area:  6400
WHOLE HOUSE Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):   HUDSON STREET,    GREENWICH STREET
Status:   C - JOB IS SIGNED OFF 10/16/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/10/2011 5:45 PM
Application Entered:   06/10/2011 Job Start Date:   06/10/2011
Last Change:   10/16/2013 Job End Date:   06/10/2012
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     09/11/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011819 Licensee Name: ROBERT A LOGOZIO
Firm: 003506 Firm Name: TEAM ELECTRIC, INC
Firm Phone: 212-685-8585  Firm Address: 20 WEST 36TH STREET, 10TH FL NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $1,381.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   RESIDENTIAL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CHRISTIAN HARKER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  3O 400AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  8  
B. Over #2 to 1/0  3  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  2  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  10  (4)42CK, (1) 24 CK, (5)8C
D. 3 Phase Over 225 AMPS  1  42 CK DP MAIN LUG PANEL
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  DISCONNECT SWITCH ONLY
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    33  20    33  16     
001    15  34      15             
002    53  50      53             
003    50  32    50             
PT1    27  14    27             
ROF                   
Buildings Total 178  151    178     23         
Total Units : 535 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/10/2011 Notice: 1 - FIRST NOTICE 06/17/2013
Power Issued: 06/10/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M315441
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/12/2012 06/21/2012 CCH J G (30) (0) Y
INSPECTION COMMENTS: JOB NOT COMPLETED
 
(2) 08/01/2012 08/13/2012 CCH J E (60) (0) Y
INSPECTION COMMENTS: NO SHOW / JOB NOT COMPLETED MAYBE 3 MTHS
 
(3) 10/11/2012 10/25/2012 CLC Z (0) (0) Y
INSPECTION COMMENTS: *CONTRACTOR CANCELED*
 
(4) 01/04/2013 01/11/2013 GYM N (35) (0) Y
INSPECTION COMMENTS: CONTRACTO NO SHOW
 
(5) 03/08/2013 03/22/2013 TSO N (25) (0) Y
INSPECTION COMMENTS: NONE
 
(6) 05/14/2013 05/22/2013 EDB N (10) (0) Y
INSPECTION COMMENTS: *NO SHOW - CANCEL*
 
(7) 06/10/2013 06/17/2013 EDB A E (120) (16) Y
INSPECTION COMMENTS: **SEE OBJECTIONS
 
(8) 09/11/2013 09/16/2013 TSO C R E (45) (0) Y
INSPECTION COMMENTS: MOST OBJECTIONS SHOULD NOT HAVE BEEN WRITTEN 2005 NEC SHOULD HAVE BEEN USED

OBJECTION FOR APPLICATION #: M315441
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: PANELS MULTIWIRE CKT NOT SIMULT TRIP...... - 210.4
RSLV 06/10/2013 06/10/2013 09/11/2013
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
BSMT: NO G.F.C.I.WITHIN 6' FROM WATER FOUNTAIN.... - 210.8
RSLV 06/10/2013 06/10/2013 09/11/2013
 
003 (340) RECEPTACLES NOT TAMPERPROOF
ALL FL: RECEPTACLE NOT TAMPER PROOF....... - 406.11
RSLV 06/10/2013 06/10/2013 09/11/2013
 
004 (999) OTHER
BSMT: STEAM RM DISC SW NOT DAMP LOCATION.... - 110.2
RSLV 06/10/2013 06/10/2013 09/11/2013
 
005 (109) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
1FL: IT ROOM FMC NOT SUPPORTED........ - 348.30
RSLV 06/10/2013 06/10/2013 09/11/2013
 
006 ( 53) GFCI HAS NOT BEEN PROVIDED
1FL: GAME RM NO G.F.C.I.WITHIN 6' FROM SINK..... - 210.8
RSLV 06/10/2013 06/10/2013 09/11/2013
 
007 (999) OTHER
ALL FL: OUTDOOR G.F.C.I.NOT WTR......... - 408.6
RSLV 06/10/2013 06/10/2013 09/11/2013
 
008 ( 19) DEFECTIVE WIRING IS IN USE
KITCHEN: OUTDOOR DEFECTIVE WIRING(OPEN NEUTRAL)..... - 110.2A
RSLV 06/10/2013 06/10/2013 09/11/2013
 
009 (311) FIXTURE NOT APPROVED FOR DAMP/WET LOCATION
3FL: BATHROOM LIGHT NOT FOR WET/DAMP LOCATION.... - 410.10
RSLV 06/10/2013 06/10/2013 09/11/2013
 
010 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
ROOF: A/C DISC SW(S)NOT PROPERLY GND/BONDED..... - 250.4A
RSLV 06/10/2013 06/10/2013 09/11/2013
 
011 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
ROOF: LIQUID TIGHT BROKER BY A/C UNIT..... - 350
RSLV 06/10/2013 06/10/2013 09/11/2013
 
012 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
ALL FL: NO A.F.C.I.PROVIDED...... - 210.12
RSLV 06/10/2013 06/10/2013 09/11/2013
 
013 (999) OTHER
ROOF: ELEV.RM DOUBLE LUG ON GND IN LIGHT DISC SW.. - 110.14A,3B
RSLV 06/10/2013 06/10/2013 09/11/2013
 
014 (181) DISCONNECTING MEANS IS IMPROPER/NOT PROVIDED
ROOF: ELEV.RM. DISC SW NOT SUPPORTED..... - 620.51
RSLV 06/10/2013 06/10/2013 09/11/2013
 
015 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
ROOF: BX RUN INSIDE LIQUID TIGHT....... - 250.4
RSLV 06/10/2013 06/10/2013 09/11/2013
 
016 (109) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
1FL: IT RM GND WIRE NOT ACCESSIBLE...... - 110.26
RSLV 06/10/2013 06/10/2013 09/11/2013