| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
3O 400AMP |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
8 |
|
| B. Over #2 to 1/0 |
3 |
|
| C. Over 1/0 to 250 MCM |
1 |
|
| D. Over 250 MCM |
2 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
10 |
(4)42CK, (1) 24 CK, (5)8C |
| D. 3 Phase Over 225 AMPS |
1 |
42 CK DP MAIN LUG PANEL |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
1 |
DISCONNECT SWITCH ONLY |
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER BSMT: PANELS MULTIWIRE CKT NOT SIMULT TRIP...... - 210.4 |
RSLV |
06/10/2013 |
06/10/2013 |
09/11/2013 |
| |
| 002 |
( 53) |
GFCI HAS NOT BEEN PROVIDED BSMT: NO G.F.C.I.WITHIN 6' FROM WATER FOUNTAIN.... - 210.8 |
RSLV |
06/10/2013 |
06/10/2013 |
09/11/2013 |
| |
| 003 |
(340) |
RECEPTACLES NOT TAMPERPROOF ALL FL: RECEPTACLE NOT TAMPER PROOF....... - 406.11 |
RSLV |
06/10/2013 |
06/10/2013 |
09/11/2013 |
| |
| 004 |
(999) |
OTHER BSMT: STEAM RM DISC SW NOT DAMP LOCATION.... - 110.2 |
RSLV |
06/10/2013 |
06/10/2013 |
09/11/2013 |
| |
| 005 |
(109) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED 1FL: IT ROOM FMC NOT SUPPORTED........ - 348.30 |
RSLV |
06/10/2013 |
06/10/2013 |
09/11/2013 |
| |
| 006 |
( 53) |
GFCI HAS NOT BEEN PROVIDED 1FL: GAME RM NO G.F.C.I.WITHIN 6' FROM SINK..... - 210.8 |
RSLV |
06/10/2013 |
06/10/2013 |
09/11/2013 |
| |
| 007 |
(999) |
OTHER ALL FL: OUTDOOR G.F.C.I.NOT WTR......... - 408.6 |
RSLV |
06/10/2013 |
06/10/2013 |
09/11/2013 |
| |
| 008 |
( 19) |
DEFECTIVE WIRING IS IN USE KITCHEN: OUTDOOR DEFECTIVE WIRING(OPEN NEUTRAL)..... - 110.2A |
RSLV |
06/10/2013 |
06/10/2013 |
09/11/2013 |
| |
| 009 |
(311) |
FIXTURE NOT APPROVED FOR DAMP/WET LOCATION 3FL: BATHROOM LIGHT NOT FOR WET/DAMP LOCATION.... - 410.10 |
RSLV |
06/10/2013 |
06/10/2013 |
09/11/2013 |
| |
| 010 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED ROOF: A/C DISC SW(S)NOT PROPERLY GND/BONDED..... - 250.4A |
RSLV |
06/10/2013 |
06/10/2013 |
09/11/2013 |
| |
| 011 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED ROOF: LIQUID TIGHT BROKER BY A/C UNIT..... - 350 |
RSLV |
06/10/2013 |
06/10/2013 |
09/11/2013 |
| |
| 012 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED ALL FL: NO A.F.C.I.PROVIDED...... - 210.12 |
RSLV |
06/10/2013 |
06/10/2013 |
09/11/2013 |
| |
| 013 |
(999) |
OTHER ROOF: ELEV.RM DOUBLE LUG ON GND IN LIGHT DISC SW.. - 110.14A,3B |
RSLV |
06/10/2013 |
06/10/2013 |
09/11/2013 |
| |
| 014 |
(181) |
DISCONNECTING MEANS IS IMPROPER/NOT PROVIDED ROOF: ELEV.RM. DISC SW NOT SUPPORTED..... - 620.51 |
RSLV |
06/10/2013 |
06/10/2013 |
09/11/2013 |
| |
| 015 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED ROOF: BX RUN INSIDE LIQUID TIGHT....... - 250.4 |
RSLV |
06/10/2013 |
06/10/2013 |
09/11/2013 |
| |
| 016 |
(109) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED 1FL: IT RM GND WIRE NOT ACCESSIBLE...... - 110.26 |
RSLV |
06/10/2013 |
06/10/2013 |
09/11/2013 |