BIS Menu  |  DOB Violations  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M315134
Premises: 90 PRINCE STREET MANHATTAN BIN: 1007586     Block: 498   Lot: 7501
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 90 PRINCE ST Census Tract:   49 Health Area:  6800
MERCER ST. AND BROADWAY Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   BROADWAY,    MERCER STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/02/2011 10:57 AM
Application Entered:   06/02/2011 Job Start Date:   06/02/2011
Last Change:   08/22/2025 Job End Date:   05/26/2012
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     05/14/2013      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  
Objection Disposition:  

License #: 010118 Licensee Name: ROBERT MARCHISOTTO
Firm: 002914 Firm Name: R.C.M. ELECTRIC CORP.
Firm Phone: 718-339-2680  Firm Address: 1915 MCDONALD AVE. BLDG REAR BROOKLYN NY 11223 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   R0 CONDOMINIUMS
Special Cert Approval:   L - FIRE ALARM LOCAL LAW #5
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: NEWBEDFORD MANAGEMENT
Authorized Representative:  PAULA RYBACZYK
Relationship To Owner:   AGENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 05/22/2013
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M315134
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/13/2012 03/24/2012 CCH N (30) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(2) 05/14/2013 05/22/2013 EDB A (40) (4) Y
INSPECTION COMMENTS: **SEE OBJECTIONS

OBJECTION FOR APPLICATION #: M315134
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
ROOF: ELEV.RM EMT NOT SUPPORTED...... - 358.30
OPEN 05/14/2013 05/14/2013
 
002 ( 29) OUTLET BOXES ARE NOT COVERED
ROOF: ELEV.RM OUTBLET BOX NOT COVERED..... - 314.25
OPEN 05/14/2013 05/14/2013
 
003 (999) OTHER
ROOF: ELEV.RM PULL L NOT ACCESSIBLE... - 110
OPEN 05/14/2013 05/14/2013
 
004 (192) CONDUCTORS ARE OVER FUSED AS PER TABLE 310.16
BSMT: #4 AWG ON 100A FUSE..... - 310.16
OPEN 05/14/2013 05/14/2013