NYC Department of Buildings
Electrical Application Details for App #: M313726
Premises: 4 EAST 43 STREET MANHATTAN BIN: 1088173     Block: 1277   Lot: 67
   
Application Completed and Certified

Filed: 4 E 43 ST Census Tract:   94 Health Area:  4800
CELLAR/ 1ST -8TH FLOOR / ROOF Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10017 Community Board:   105
Special Place Name:   VON POK & CHANG
DOB Cross Street(s):    5 AVENUE,    MADISON AVENUE
Status:   C - JOB IS SIGNED OFF 11/21/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/19/2011 4:15 PM
Application Entered:   04/19/2011 Job Start Date:   04/19/2011
Last Change:   11/21/2012 Job End Date:   04/19/2013
Appointment Status:   
Last Inspection By:   BINGEL, LORI       On     09/06/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011484 Licensee Name: EUGENE C ECCLES
Firm: 003560 Firm Name: JEMINIS ELEC'L CONTRS INC
Firm Phone: 718-326-2000  Firm Address: 58-38 59TH STREET -SUITE 2 MASPETH NY 11378 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $1,796.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CHANG OMEGA
Owner Business Name: VON POK INC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  2  
C. 201 Up to 600 AMPS  3  
D. 601 Up to 1200 AMPS  1  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  3  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  9  
D. 3 Phase Over 225 AMPS  3  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    31  29    16    11         
001    25  18                 
002    19                 
003    28  29                 
004    28  27                 
005    28  27                 
006    28  27                 
007    17  38    11               
008    13      10         
ROF                       
Buildings Total 202  233    78       21           
Total Units : 534 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 6 #10-Wire 2
Existing Meters 4 + New Meters 8 - Removed Meters 4 = Total Meters 8

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/19/2011 Notice: 1 - FIRST NOTICE 06/14/2012
Power Issued: 04/19/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M313726
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/04/2012 06/14/2012 RID V D (124) (10) Y
INSPECTION COMMENTS: X
 
(2) 08/06/2012 08/18/2012 GYM J Y E (80) (0) Y
INSPECTION COMMENTS: NONE
 
(3) 09/06/2012 09/08/2012 LBI C R E (110) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M313726
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BASEMENT ALL SERVICE SWITCHES 250.56NEUTRAL BAR NOT BONDED TO ENCLOSURE
RSLV 06/04/2012 08/06/2012 09/06/2012
 
002 (999) OTHER
BASEMENT LIMITED FIRE PUMMP IS NOT 150% 695.4B
RSLV 06/04/2012 08/06/2012 09/06/2012
 
003 (999) OTHER
BASEMENT SERVICE ENTRANCE CONDUCTOR 250.66NOT PROPERLY GROUNDED
RSLV 06/04/2012 08/06/2012 09/06/2012
 
004 (999) OTHER
BASEMENT SERVICE SWITCHE FOR 3=FT TO 8TH FLOOR 240OVER FUSES. 350 MCM. FUSE AT 600
RSLV 06/04/2012 08/06/2012 09/06/2012
 
005 (999) OTHER
BASEMENT SERVICE ENTRANCE CONDUCTOR FOR 1 FLOOR. 2 FLOOR UNDER SIZE250.66
RSLV 06/04/2012 08/06/2012 09/06/2012
 
006 (999) OTHER
BASEMENT BOILER ROOM. NO GFCI PROVIDED 620.22B
RSLV 06/04/2012 08/06/2012 09/06/2012
 
007 (999) OTHER
ALL FLOOR VERTICAL RACEWAY 300.19NO SUPPORT FOR VERTICAL RACEWAY
RSLV 06/04/2012 06/04/2012 08/06/2012
 
008 (999) OTHER
LIMITED FIRE PUMP RACEWAY 695COMPLIANCE NOT STEEL AND CONNECTORS
RSLV 06/04/2012 08/06/2012 09/06/2012
 
009 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
ALL FLOORS SUB PANELSNO DIRECTORY PROVIDED
RSLV 06/04/2012 06/04/2012 08/06/2012
 
010 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ROOF TOP A/C UNITSNOT GROUNDED. INSPECTION NOT FINAL
RSLV 06/04/2012 08/06/2012 09/06/2012