BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M313661
Premises: 34 RIVER TERRACE MANHATTAN BIN: 1085774     Block: 16   Lot: 200
   
Application Completed and Certified

Filed: 400 CHAMBERS ST Census Tract:   317.01 Health Area:  8900
GROUND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10282 Community Board:   101
DOB Cross Street(s):   NORTH END AVENUE,    RIVER TERRACE
Status:   C - JOB IS SIGNED OFF 08/28/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/18/2011 10:10 AM
Application Entered:   04/18/2011 Job Start Date:   04/18/2011
Last Change:   08/28/2012 Job End Date:   12/31/2011
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     08/13/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011281 Licensee Name: MIKHAIL RABINOVICH
Firm: 002683 Firm Name: KINGS ELECTRIC CO., INC.
Firm Phone: 718-209-8439  Firm Address: 6921 8TH AVENUE BROOKLYN NY 11228 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $66.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: FINIX U.S.A. CONSTRUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    40  20    10  40         
Buildings Total 40  20    10  40              
Total Units : 114 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/20/2012
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  MEDICAL OFFICE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M313661
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/04/2011 10/19/2011 CCH N (30) (0) Y
INSPECTION COMMENTS: NONE
 
(2) 03/09/2012 03/20/2012 GYM A (80) (3) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(3) 08/13/2012 08/24/2012 DAH C R (90) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M313661
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
GROUND FL: METAL RACEWAY IS NOT PROVIDED FOR EXAM ROOMS 1,2,3(MC CABLE USED)....... - ART.517.13
RSLV 03/09/2012 03/09/2012 08/13/2012
 
002 (999) OTHER
GROIND FL: RECEPTACLE AT PATIENT BED IS NOT HOSPITAL GRADE(EXAM ROOMS 1,2,3)...... - ART.517.12B
RSLV 03/09/2012 03/09/2012 08/13/2012
 
003 ( 53) GFCI HAS NOT BEEN PROVIDED
GROUND FL: CLOSET WITH SINK
RSLV 03/09/2012 03/09/2012 08/13/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back