Electrical Application Details for App #: M313061
Premises: 120 EAST 4 STREET MANHATTAN BIN: 1083152     Block: 445   Lot: 26
   
Application Completed and Certified

Filed: 120 E 4TH ST Census Tract:   3800 Health Area:  6500
1ST Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10003 Community Board:   103
DOB Cross Street(s):    2 AVENUE,    1 AVENUE
Status:   C - JOB IS SIGNED OFF 11/15/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/01/2011 10:01 AM
Application Entered:   04/01/2011 Job Start Date:   04/04/2011
Last Change:   11/15/2012 Job End Date:   04/15/2012
Appointment Status:   
Last Inspection By:   BEST, J       On     07/07/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009639 Licensee Name: THOMAS S CARNEY
Firm: 003614 Firm Name: ROYAL ELEC'L & WIRING COR
Firm Phone: 718-584-1424  Firm Address: 2558 MARION AVENUE 1 BRONX NY 10458 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,859.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BEN SHAOUL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  1#100A
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  2 #400A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  45  35#8/3, 10# 6/3
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  SET 500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  45  12 CKT
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  3 PHASE 100A 30 CKT
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    12  13  12             
MZ1    12  13  12             
MZ2    24  26  10  24             
MZ3    12  13  12             
Buildings Total 60  65  25  60                
Total Units : 215 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 45 #4-Wire 1 #10-Wire 0
Existing Meters 46 + New Meters 46 - Removed Meters 46 = Total Meters 46

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/01/2011 Notice: 1 - FIRST NOTICE 03/16/2012
Power Issued: 04/01/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M313061
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/06/2012 03/16/2012 GYM V E (115) (7) Y
INSPECTION COMMENTS: NONE
 
(2) 07/07/2012 08/07/2012 JSB C R E (45) (0) Y
INSPECTION COMMENTS: X

OBJECTION FOR APPLICATION #: M313061
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT,ART.250.28,400AMP SER SWS NEUTRAL BAR IS NOT BONDED
RSLV 03/06/2012 03/06/2012 07/07/2012
 
002 (999) OTHER
BSMT,TAB 250.66 GROUNDING ELECTRODE CONDUCTOR UNDERSIZE
RSLV 03/06/2012 03/06/2012 07/07/2012
 
003 (999) OTHER
A)ART.250.64 GROUNDING RACEWAY IS NOT CONDINIOUS EMT TUBING
RSLV 03/06/2012 03/06/2012 07/07/2012
 
004 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BSMT,DEFECTIVE GROUNDING CLAMP AT WATER MAIN
RSLV 03/06/2012 03/06/2012 07/07/2012
 
005 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
BSMT APTS FEEDERS THRU OUT
RSLV 03/06/2012 03/06/2012 07/07/2012
 
006 (999) OTHER
B)BSMT ART 300.21 APTS RISERS IN A BONDED DUMB WAITER SHAFT NOT FIRM STOPPED
RSLV 03/06/2012 03/06/2012 07/07/2012
 
007 (999) OTHER
BSMT,ART 250.24 METER PAN NEUTRAL BAR BONDED AFTER S.S
RSLV 03/06/2012 03/06/2012 07/07/2012