BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M312289
Premises: 139 CENTRE STREET MANHATTAN BIN: 1002357     Block: 197   Lot: 7502
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 139 CENTRE ST Census Tract:   3100 Health Area:  7700
GROUND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   101
DOB Cross Street(s):   WHITE STREET,    WALKER STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/14/2011 8:56 AM
Application Entered:   03/14/2011 Job Start Date:   03/14/2011
Last Change:   08/22/2025 Job End Date:   05/14/2011
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     01/24/2013      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 010606 Licensee Name: MYRON COHEN
Firm: 003435 Firm Name: A.T. ELEC'L CONTR'G, INC
Firm Phone: 718-234-9250  Firm Address: 1561 64TH STREET BROOKLYN NY 11219 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $134.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   PHARMACY
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOHN AU
Owner Business Name: ABC PHARMACY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  2  #3/4 WIRE
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    12    40  25         
Buildings Total 12    40     25           
Total Units : 87 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 02/21/2013
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M312289
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/24/2013 02/21/2013 CLC V (45) (7) Y
INSPECTION COMMENTS: *INSPECT ENTIRE JOB OVER PHARMACY AND REST. - CHECK ALL COVE LIGHTING *SEE OBJECTIONS

OBJECTION FOR APPLICATION #: M312289
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
ENTIRE: ALL LIGHTING FLEXIBLE CORDS USED FOR WIRING
OPEN 01/24/2013 01/24/2013
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ENTIRE: ALL LIGHTING BX CABLE NOT GNDED TO FIXTURES
OPEN 01/24/2013 01/24/2013
 
003 (999) OTHER
1ST FL: G.F.C.I.NOT PROVIDED WITHIN 6' OF SINK
OPEN 01/24/2013 01/24/2013
 
004 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
REST: PANEL 10 WIRE FUSED AT 40 AMPS
OPEN 01/24/2013 01/24/2013
 
005 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
1ST FL: PANELS NOT LABEL
OPEN 01/24/2013 01/24/2013
 
006 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
1ST FL: REST DOOR WAY FLEXIBLE CORD USED TO FEED SIGN
OPEN 01/24/2013 01/24/2013
 
007 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ENTIRE: HIGH HATS BX CABLES NOT GNED TO FIXTURESBRANCH CKTS NOT PROPERLY TERMINATED
OPEN 01/24/2013 01/24/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order