BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M312050
Premises: 15 ESSEX STREET MANHATTAN BIN: 1083702     Block: 297   Lot: 22
   

DOB NOW: Inspections


Filed: 15 ESSEX ST Census Tract:   1600 Health Area:  7400
APT. # 22, #23, #14, #11 Admin Area:   M - MANHATTAN Inspection Area:   V
NEW YORK, NY 10002 Community Board:   103
DOB Cross Street(s):   CANAL STREET,    HESTER STREET
Status:   C - SIGNOFF IS AWAITING FEE PAYMENT 06/02/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/07/2011 9:25 AM
Application Entered:   03/07/2011 Job Start Date:   03/07/2011
Last Change:   06/02/2016 Job End Date:   03/06/2012
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     06/01/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011721 Licensee Name: CHRISTOPHER PACCIONE
Firm: 003156 Firm Name: CHRISTOPHER JON ELEC'L
Firm Phone: 718-389-9898  Firm Address: 513 13TH STREET STORE WEST CONTRACTORS, INC. NEW YORK NY 10009 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $899.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (2  Stores, 22 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GREEN LEAF ASSOCIATES LLC
Owner Business Name: GREEN LEAF ASSOCIATES LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  22  
B. Over #2 to 1/0  2  
C. Over 1/0 to 250 MCM  2  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  4  
C. 3 Phase Up to 225 AMPS  2  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  #11  12             
001  #14  12             
001  #22  12             
001  #23  12             
Buildings Total 16  48  12  16  16                
Total Units : 108 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 23 #4-Wire 2 #10-Wire 0
Existing Meters 25 + New Meters 25 - Removed Meters 25 = Total Meters 25

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/07/2011 Notice: 1 - FIRST NOTICE 03/08/2016
Power Issued: 03/07/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M312050
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/06/2012 04/14/2012 CCH N (30) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(2) 12/02/2015 12/03/2015 UMS N (35) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW,CONTRACTOR FORGOT ABOUT APPOINTMENT
 
(3) 12/08/2015 12/09/2015 CBK N (150) (0) Y
INSPECTION COMMENTS: ELECTRICIAN DID NOT SHOW UP
 
(4) 12/23/2015 02/22/2016 CBK V (60) (6)
INSPECTION COMMENTS: INSPECTION FAILED. ONLY INSPECT APT. #11 AND BSMT. DID NOT INSPECT APT. #14, #22 AND #23.
 
(5) 03/08/2016 03/08/2016 STP V Y (45) (6)
INSPECTION COMMENTS: APT 23 PANEL BEHIND BED TOTALLY BLOCKED.
 
(6) 06/01/2016 06/02/2016 TOR C R (30) (0)
INSPECTION COMMENTS: OBJECTIONS ONLY.

OBJECTION FOR APPLICATION #: M312050
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 001) AFCI NEEDED IN PANEL APT. #11
RSLV 12/23/2015 12/23/2015 03/08/2016
 
002 (999) OTHER
(FLOOR: 001) RECEPTACLES NOT OF THE TR TYPE. 406.11 APT.#11.
RSLV 12/23/2015 12/23/2015 06/01/2016
 
003 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(BASEMENT) BREAKER BLANKS NEEDED. 110.12(A)
RSLV 12/23/2015 12/23/2015 03/08/2016
 
004 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(BASEMENT) NO DIRECTORY PROVIDED IN PANELS. 408.4
RSLV 12/23/2015 12/23/2015 06/01/2016
 
005 (999) OTHER
(BASEMENT) DOUBLE LUGGED IN PANEL. 110.3
RSLV 12/23/2015 12/23/2015 03/08/2016
 
006 (999) OTHER
(BASEMENT) SIMULTANEOUS TRIP NEEDED IN PANEL
RSLV 12/23/2015 12/23/2015 03/08/2016
 
007 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(FLOOR: 004) APT 14, APT 22 KITCHEN COUNTER BAD GFI. 210.8
RSLV 03/08/2016 03/08/2016 06/01/2016
 
008 (999) OTHER
(FLOOR: 004) APT 14, 22 , 23NO T.R. OUTLETS PROVIDED. 210.12
RSLV 03/08/2016 03/08/2016 06/01/2016
 
009 (999) OTHER
(FLOOR: 004) APT 14 , APT 22 NO DIRECTORY FOR PANEL 408.4
RSLV 03/08/2016 03/08/2016 06/01/2016
 
010 (999) OTHER
(FLOOR: 006) APT 22 NO TIE HANDLE IN PANEL 210.4
RSLV 03/08/2016 03/08/2016 06/01/2016
 
011 (999) OTHER
(FLOOR: 006) APT 23 PANEL IN CLOTHES CLOSET 240.24.D
RSLV 03/08/2016 03/08/2016 06/01/2016
 
012 (999) OTHER
(FLOOR: 006) APT 23 NO WORKING SPACE FOR PANE 110.26
RSLV 03/08/2016 03/08/2016 06/01/2016