Premises: 61 5 AVENUE MANHATTAN BIN: 1009376     Block: 570   Lot: 7
   
Application Completed and Certified

Filed: 61 5TH AV Census Tract:   6100 Health Area:  5700
CELLAR, 1ST-11TH FLRS & ROOF Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
Related Job Number:    110296750
DOB Cross Street(s):   EAST 12 STREET,    EAST 13 STREET
Status:   C - JOB IS SIGNED OFF 11/20/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/01/2011 11:28 AM
Application Entered:   03/01/2011 Job Start Date:   03/01/2011
Last Change:   11/20/2014 Job End Date:   03/01/2012
Appointment Status:   
Last Inspection By:   RIVERA, F       On     11/12/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010863 Licensee Name: JOHN M DELUCA
Firm: 002448 Firm Name: DELCO ELECTRICAL CORP.
Firm Phone: 212-221-0068  Firm Address: 4233 ARTHUR KILL ROAD, STE 2A STATEN ISLAND NY 10309 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
2 - TEMPORARY CONSTRUCTION
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $1,843.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 4 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MAREK KIYASHKA
Owner Business Name: 61 5TH AVENUE, LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  2  2 @ 200 AMPS
C. 201 Up to 600 AMPS  2  2 @ 400 AMPS
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  8  APT PNLS & SUB PNLS
B. Over #2 to 1/0  1  P/H APT MAIN PNL
C. Over 1/0 to 250 MCM  11  
D. Over 250 MCM  2  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  8  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  
C. 3 Phase Up to 225 AMPS  4  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    40  16    19    10  50         
001    44  10    44             
002    49  39    20  49             
003    40  32    25  40             
004    49  39    20  49             
005    40  32    25  40             
006    49  39    20  49             
007    40  32    25  40             
008    46  33    21  46             
009    45  30    20  45             
010    38  25    22  38             
011                     
ROF                       
Buildings Total 480  334    230  440     50           
Total Units : 1534 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 4 #4-Wire 2 #10-Wire 1
Existing Meters 1 + New Meters 6 - Removed Meters 0 = Total Meters 7

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/01/2011 Notice: 1 - FIRST NOTICE 10/31/2014
Power Issued: 03/01/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M311878
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/06/2014 10/15/2014 NRS V G (130) (14) Y
INSPECTION COMMENTS: ELECTRICAL ROOM INSPECTED,EXCEPT PL-C PANEL
 
(2) 10/28/2014 10/31/2014 EID V Y G (115) (7) Y
INSPECTION COMMENTS: INSPECTED BSMT,ROOF,10TH FL NOT INSPECTED ALL OTHER FLRS.BRANCH CKT AND CKT BKR PNL ON ROOF
 
(3) 11/12/2014 11/20/2014 FRI C R E (75) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M311878
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
CELL: TROUGH ABOVE 2-4-6 PL METERS & DISCONNECTS BELOW BONDING JUMP-ER NOT AS PER 250.122
RSLV 10/06/2014 10/28/2014 11/12/2014
 
002 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
CELL: RETAIL SERVICE DISCONNECT
RSLV 10/06/2014 10/28/2014 11/12/2014
 
003 (125) PROTECTION OF CONDUCTORS NOT INSTALLED AS PER CODE
CELL: PP-C 200A SWITCH NOT SIZED AS PER 310.16
RSLV 10/06/2014 10/28/2014 11/12/2014
 
004 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
CELL: 2 100A FUSED PUMP. E.G.C. NOT AS PER 250.122
RSLV 10/06/2014 10/28/2014 11/12/2014
 
005 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
CELL: SERVICE SWITCH (BOARD 400A) NOT INSTALLED
RSLV 10/06/2014 10/06/2014 10/28/2014
 
006 (999) OTHER
CELL: FIRE ALARM SERV.DISC.G.E.C. NOT TERMINATED AS PER 250.25(A)(4)
RSLV 10/06/2014 10/06/2014 10/28/2014
 
007 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
CELL: PP-C RIGHT SIDE 2" ON TOP
RSLV 10/06/2014 10/06/2014 10/28/2014
 
008 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
CELL: PP-C PANEL
RSLV 10/06/2014 10/28/2014 11/12/2014
 
009 (125) PROTECTION OF CONDUCTORS NOT INSTALLED AS PER CODE
CELL: PP-C LEFT BOTTOM 50A 2 POLE BREAKER (TT10 AWG)
RSLV 10/06/2014 10/06/2014 10/28/2014
 
010 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
CELL: RETAIL SERVICE SWITCH NOT INSTALLED
RSLV 10/06/2014 10/06/2014 10/28/2014
 
011 (280) MAIN BONDING JUMPER IS DEFECTIVE
CELL: 400A SERVICE SWITCH BOARD
RSLV 10/06/2014 10/06/2014 10/28/2014
 
012 (125) PROTECTION OF CONDUCTORS NOT INSTALLED AS PER CODE
CELL: 8TH FLOOR DISCONNECT NOT FUSED AS PER 310.16
RSLV 10/06/2014 10/06/2014 10/28/2014
 
013 (999) OTHER
CELL: 2" PUMP DISCONNECT NOT FUSED AS PER 430.52
RSLV 10/06/2014 10/06/2014 10/28/2014
 
014 (999) OTHER
CELL: FIRE ALARM SUPPLY TAP ON LOAD SIDE OF SERVICE SWITCHAM.760.41
RSLV 10/06/2014 10/28/2014 11/12/2014
 
015 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
ROOF: MC CABLE NOT PROPERLY TERMINATED IN ROOF FAN. 320.40
RSLV 10/28/2014 10/28/2014 11/12/2014
 
016 (999) OTHER
ROOF: G.F.C.I.OUTDOOR NEEDS IN-USE COVERS. 406.8
RSLV 10/28/2014 10/28/2014 11/12/2014
 
017 (999) OTHER
ROOF: A/C UNIT NOT FUSED AS PER MAN.SPEC. AMD 110.2
RSLV 10/28/2014 10/28/2014 11/12/2014
 
018 (999) OTHER
10TH FL: A/C UNITS 2 NOT FUSED AS PER MAN.SPEC. AMD 110.2
RSLV 10/28/2014 10/28/2014 11/12/2014
 
019 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
10TH FL: A.F.C.I.NOT PROVIDED FOR BED RM CKTS. 210.12B
RSLV 10/28/2014 10/28/2014 11/12/2014
 
020 (999) OTHER
10TH FL: G.F.C.I.RECEP.SET BACK MORE THAN 1/4". 314.20
RSLV 10/28/2014 10/28/2014 11/12/2014
 
021 (999) OTHER
10TH FL: PNL NOT PROVIDED WITH A DIRECTORY. 408.4
RSLV 10/28/2014 10/28/2014 11/12/2014