| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
2 |
2 @ 200 AMPS |
| C. 201 Up to 600 AMPS |
2 |
2 @ 400 AMPS |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
8 |
APT PNLS & SUB PNLS |
| B. Over #2 to 1/0 |
1 |
P/H APT MAIN PNL |
| C. Over 1/0 to 250 MCM |
11 |
|
| D. Over 250 MCM |
2 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
8 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
1 |
|
| C. 3 Phase Up to 225 AMPS |
4 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED CELL: TROUGH ABOVE 2-4-6 PL METERS & DISCONNECTS BELOW BONDING JUMP-ER NOT AS PER 250.122 |
RSLV |
10/06/2014 |
10/28/2014 |
11/12/2014 |
| |
| 002 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER CELL: RETAIL SERVICE DISCONNECT |
RSLV |
10/06/2014 |
10/28/2014 |
11/12/2014 |
| |
| 003 |
(125) |
PROTECTION OF CONDUCTORS NOT INSTALLED AS PER CODE CELL: PP-C 200A SWITCH NOT SIZED AS PER 310.16 |
RSLV |
10/06/2014 |
10/28/2014 |
11/12/2014 |
| |
| 004 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED CELL: 2 100A FUSED PUMP. E.G.C. NOT AS PER 250.122 |
RSLV |
10/06/2014 |
10/28/2014 |
11/12/2014 |
| |
| 005 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY CELL: SERVICE SWITCH (BOARD 400A) NOT INSTALLED |
RSLV |
10/06/2014 |
10/06/2014 |
10/28/2014 |
| |
| 006 |
(999) |
OTHER CELL: FIRE ALARM SERV.DISC.G.E.C. NOT TERMINATED AS PER 250.25(A)(4) |
RSLV |
10/06/2014 |
10/06/2014 |
10/28/2014 |
| |
| 007 |
( 21) |
CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED CELL: PP-C RIGHT SIDE 2" ON TOP |
RSLV |
10/06/2014 |
10/06/2014 |
10/28/2014 |
| |
| 008 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY CELL: PP-C PANEL |
RSLV |
10/06/2014 |
10/28/2014 |
11/12/2014 |
| |
| 009 |
(125) |
PROTECTION OF CONDUCTORS NOT INSTALLED AS PER CODE CELL: PP-C LEFT BOTTOM 50A 2 POLE BREAKER (TT10 AWG) |
RSLV |
10/06/2014 |
10/06/2014 |
10/28/2014 |
| |
| 010 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY CELL: RETAIL SERVICE SWITCH NOT INSTALLED |
RSLV |
10/06/2014 |
10/06/2014 |
10/28/2014 |
| |
| 011 |
(280) |
MAIN BONDING JUMPER IS DEFECTIVE CELL: 400A SERVICE SWITCH BOARD |
RSLV |
10/06/2014 |
10/06/2014 |
10/28/2014 |
| |
| 012 |
(125) |
PROTECTION OF CONDUCTORS NOT INSTALLED AS PER CODE CELL: 8TH FLOOR DISCONNECT NOT FUSED AS PER 310.16 |
RSLV |
10/06/2014 |
10/06/2014 |
10/28/2014 |
| |
| 013 |
(999) |
OTHER CELL: 2" PUMP DISCONNECT NOT FUSED AS PER 430.52 |
RSLV |
10/06/2014 |
10/06/2014 |
10/28/2014 |
| |
| 014 |
(999) |
OTHER CELL: FIRE ALARM SUPPLY TAP ON LOAD SIDE OF SERVICE SWITCHAM.760.41 |
RSLV |
10/06/2014 |
10/28/2014 |
11/12/2014 |
| |
| 015 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED ROOF: MC CABLE NOT PROPERLY TERMINATED IN ROOF FAN. 320.40 |
RSLV |
10/28/2014 |
10/28/2014 |
11/12/2014 |
| |
| 016 |
(999) |
OTHER ROOF: G.F.C.I.OUTDOOR NEEDS IN-USE COVERS. 406.8 |
RSLV |
10/28/2014 |
10/28/2014 |
11/12/2014 |
| |
| 017 |
(999) |
OTHER ROOF: A/C UNIT NOT FUSED AS PER MAN.SPEC. AMD 110.2 |
RSLV |
10/28/2014 |
10/28/2014 |
11/12/2014 |
| |
| 018 |
(999) |
OTHER 10TH FL: A/C UNITS 2 NOT FUSED AS PER MAN.SPEC. AMD 110.2 |
RSLV |
10/28/2014 |
10/28/2014 |
11/12/2014 |
| |
| 019 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED 10TH FL: A.F.C.I.NOT PROVIDED FOR BED RM CKTS. 210.12B |
RSLV |
10/28/2014 |
10/28/2014 |
11/12/2014 |
| |
| 020 |
(999) |
OTHER 10TH FL: G.F.C.I.RECEP.SET BACK MORE THAN 1/4". 314.20 |
RSLV |
10/28/2014 |
10/28/2014 |
11/12/2014 |
| |
| 021 |
(999) |
OTHER 10TH FL: PNL NOT PROVIDED WITH A DIRECTORY. 408.4 |
RSLV |
10/28/2014 |
10/28/2014 |
11/12/2014 |