BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M311665
Premises: 185 MOTT STREET MANHATTAN BIN: 1007186     Block: 480   Lot: 33
   
Application Completed and Certified

Filed: 64 KENMARE ST Census Tract:   4100 Health Area:  6800
FIRST FLOOR Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   MOTT STREET,    MULBERRY STREET
Status:   C - JOB IS SIGNED OFF 08/26/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/22/2011 11:12 PM
Application Entered:   02/22/2011 Job Start Date:   02/28/2011
Last Change:   08/26/2014 Job End Date:   06/10/2011
Appointment Status:   
Last Inspection By:   AGELONIAS, ANASTASIOS       On     10/22/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012056 Licensee Name: VLADIMIR DOTSENKO
Firm: 001818 Firm Name: OLYMPIC ELECT WIRING CORP
Firm Phone: 718-768-2262  Firm Address: 133 50TH STREET BROOKLYN NY 11232 

Other Licensees and Firms:
License # Licensee Name Firm # Firm Name Type
011416 KOLKER, MIKHAIL 001818 OLYMPIC ELECT WIRING CORP RESPONSIBLE REP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $173.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: STEPHEN PORTO
Owner Business Name: ASIADOG, LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200 AMP
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  4#2/0 AWG
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  42 CB
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                 
001         
Buildings Total 10  13    10            
Total Units : 45 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/22/2011 Notice: 1 - FIRST NOTICE 07/30/2013
Power Issued: 02/22/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  GENERAL WIRING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M311665
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/24/2013 07/30/2013 IOS A E (70) (5) Y
INSPECTION COMMENTS: NONE
 
(2) 10/22/2013 10/30/2013 IOS C R E (60) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M311665
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (228) USING PANEL AS A RACEWAY
USING PANEL AS A RACEWAY IN STORE BASEMENT
RSLV 07/24/2013 07/24/2013 10/22/2013
 
002 ( 29) OUTLET BOXES ARE NOT COVERED
SPLICE BOX IN BASEMENT IS NOT COVERED
RSLV 07/24/2013 07/24/2013 10/22/2013
 
003 ( 6) FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION
LOAD CALCULATIONS REQUIRED FOR 500 MCM FEEDER
RSLV 07/24/2013 07/24/2013 10/22/2013
 
004 (286) NO GFCI IN COMMERCIAL KITCHEN
NO GFCI RECEPTACLE ADJACENT SINK IN BASEMENT
RSLV 07/24/2013 07/24/2013 10/22/2013
 
005 (999) OTHER
CONDUIT FOR LIGHTING RUNNING INSIDE HOOD. 410.10(C)(4)
RSLV 07/24/2013 07/24/2013 10/22/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.