Electrical Application Details for App #: M311225
Premises: 401 WEST 25 STREET MANHATTAN BIN: 1089398     Block: 723   Lot: 15
   
Application Completed and Certified

Filed: 401 W 25TH ST Census Tract:   9300 Health Area:  5200
NEW CONSTRUCTION Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   104
Related Job Number:    120299275
DOB Cross Street(s):    9 AVENUE,    10 AVENUE
Status:   C - JOB IS SIGNED OFF 09/19/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/09/2011 9:42 AM
Application Entered:   02/09/2011 Job Start Date:   02/09/2011
Last Change:   09/19/2012 Job End Date:   12/31/2013
Appointment Status:   
Last Inspection By:   BEST, J       On     09/11/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009441 Licensee Name: ANTHONY G FERRY
Firm: 000138 Firm Name: ANTHONY G FERRY INC
Firm Phone: 646-678-3795  Firm Address: 314 CITY ISLAND AVENUE BRONX NY 10464 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (4  Stores, 160 Apartments)
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval # / Submittal #:   10A0402
Owner / Occup: AMNON SOLOMON
Owner Business Name: ARTIMUS CONSTRUCTION
Authorized Representative:  AMNON SOLOMON
Relationship To Owner:   MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  3  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  110  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  5  5 SETS
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  110  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  6  
D. 3 Phase Over 225 AMPS  4  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  4  (INSIDE ELEVATORS)
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                       
MZ1    672    172  1000    250  10  15     
Buildings Total 673    172  1000       250     15      
Total Units : 2110 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 168 #4-Wire 0 #10-Wire 4
Existing Meters 0 + New Meters 172 - Removed Meters 0 = Total Meters 172

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/09/2011 Notice: 1 - FIRST NOTICE 08/17/2012
Power Issued: 02/09/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M311225
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/10/2012 05/25/2012 FRI A E (180) (3) Y
INSPECTION COMMENTS: *CAL.#50384 HAS BEEN VOIDED - REPLACED BY 51051* SEE VIOLATION DETAILS
 
(2) 08/07/2012 08/17/2012 JSB A R E (120) (4) Y
INSPECTION COMMENTS: N/A
 
(3) 09/11/2012 09/18/2012 JSB C R E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M311225
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 53) GFCI HAS NOT BEEN PROVIDED
THROUGH-OUT: KITCHEN COUNTERS
RSLV 05/10/2012 05/10/2012 08/07/2012
 
002 (999) OTHER
ALL APT.PNLS: NEUTRAL BONDED TO ENCLOSURE...... - 250.24A5
RSLV 05/10/2012 05/10/2012 08/07/2012
 
003 (999) OTHER
THROUGH-OUT ALL APT: RECEPTACLES NOT PROPERLY BONDED.... - 250.146
RSLV 05/10/2012 05/10/2012 08/07/2012
 
004 (999) OTHER
ALL SUB GEAR FEEDERS EQUIPT GRD UNDERSIZED 250.122
RSLV 08/07/2012 08/07/2012 09/11/2012
 
005 (999) OTHER
SD RM DOOR NOT EQUIPED WITH PANIC BARS 110.26(C)(2)
RSLV 08/07/2012 08/07/2012 09/11/2012
 
006 (999) OTHER
FP FEEDER FROM CNTROLLER TO MOTOR NOT RMC 695.6(D)
RSLV 08/07/2012 08/07/2012 09/11/2012
 
007 (999) OTHER
GEN FEEDER RACEWAY EMT USED OUTDOOR 358.12(7) NYC AMENDMENT
RSLV 08/07/2012 08/07/2012 09/11/2012