BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M310671
Premises: 1522 1 AVENUE MANHATTAN BIN: 1050357     Block: 1559   Lot: 50
   
Application Completed and Certified

Filed: 1522 1 AV Census Tract:   1360 Health Area:  3800
2N & 3N Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10075 Community Board:   108
DOB Cross Street(s):   EAST 79 STREET,    EAST 80 STREET
Status:   C - JOB IS SIGNED OFF 02/17/2011
Request Type:   P - PICK-UP eFiled:   YES
Application Entered:   01/26/2011 Job Start Date:   01/26/2011
Last Change:   02/17/2011 Job End Date:   03/15/2011
Appointment Status:   
Last Inspection By:   DORSAINVILLE, R       On     02/05/2011      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011360 Licensee Name: SERVULUS BILLY
Firm: 003868 Firm Name: POWERONE ELECT'L CONTRG
Firm Phone: 718-241-3236  Firm Address: 1459 BASSETT AVENUE INC BRONX NY 10461 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $105.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 6 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: RAINBOW HOLDING LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002  2N  10  50      10             
003  3N  10  50      10             
Buildings Total 20  100      20                
Total Units : 140 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  01/20/2011
Power Issued: Response: V - OBJ WAS REMOVED 02/08/2011

Follow-Up: X - FILED APPL,NOW CLOSED 01/26/2011
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M310671
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/14/2011 01/20/2011 WMK W (10) (4)
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 02/05/2011 02/10/2011 RID C R (45) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M310671
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
FOR REWIRING KITCHEN AND BATHROOM IN APARTMENTS 2N & 3N
RSLV 01/14/2011 01/14/2011 02/05/2011
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
APT.2N: G.F.C.I.RECPTACLES NOT PROVIDED
RSLV 01/14/2011 01/14/2011 02/05/2011
 
003 (999) OTHER
APTS.2N & 3N: KITCHEN - INSUFFICIENT COUNTER OUTLETS..... -*ART.210.52(B)*
RSLV 01/14/2011 01/14/2011 02/05/2011
 
004 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
BASEMENT CEILING
RSLV 01/14/2011 01/14/2011 02/05/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order