NYC Department of Buildings
Electrical Application Details for App #: M310538
Premises: 51 BANK STREET MANHATTAN BIN: 1011388     Block: 624   Lot: 53
   
Application Completed and Certified

Filed: 51 BANK ST Census Tract:   7700 Health Area:  6100
GROUND,BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):   WEST 4 STREET,    BLEECKER STREET
Status:   C - JOB IS SIGNED OFF 08/14/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/14/2011 2:47 PM
Application Entered:   01/14/2011 Job Start Date:   01/14/2011
Last Change:   08/14/2012 Job End Date:   08/15/2011
Appointment Status:   
Last Inspection By:   MCKENZIE, W.       On     07/19/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012359 Licensee Name: JOHN S KARALIS
Firm: 003811 Firm Name: TRIBORO ELEC'L CONTR'G CO
Firm Phone: 718-786-0913  Firm Address: 39-02 29TH STREET LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $536.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOE MENDLER
Owner Business Name: HM VILLAGE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  2-30A FC
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  SETS 3/0
D. Over 250 MCM  1  4 #500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  2-200A
D. 3 Phase Over 225 AMPS  1  1-400 DP
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    12      12             
GND    40  35    40  10         
Buildings Total 52  35    52     10           
Total Units : 152 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/14/2011 Notice: 1 - FIRST NOTICE 02/22/2012
Power Issued: 01/14/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M310538
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/29/2011 09/06/2011 CCH V G (60) (3) Y
INSPECTION COMMENTS: NO ACCESS TO SER SWITCH ,PANEL, WATERGROUND,AC UNITS REG AND CEILING 99
 
(2) 12/09/2011 12/22/2011 GYM V R E (65) (4) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(3) 02/09/2012 02/22/2012 CCH A R G (30) (3) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(4) 07/19/2012 08/14/2012 WMK C R E (10) (0) Y
INSPECTION COMMENTS: SEE CAL. #51220

OBJECTION FOR APPLICATION #: M310538
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
1ST FLOOR - HANGING FIXTURES NO GROUNDING
RSLV 08/29/2011 08/29/2011 12/09/2011
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
BASEMENT - OUTLET NOT GFCI PROTECTED
RSLV 08/29/2011 08/29/2011 12/09/2011
 
003 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BASEMENT FUSE CUT OUTBOX RACEWAY NOT BONDED
RSLV 08/29/2011 08/29/2011 12/09/2011
 
004 (999) OTHER
BSMT: SERVICE SWS NOT GROUPED
RSLV 12/09/2011 12/09/2011 02/09/2012
 
005 (999) OTHER
BSMT: ALL AREA WITH MC CABLE OUTLET BOXES ARE NOT BONDED BSMT 1STFLOOR
RSLV 12/09/2011 12/09/2011 02/09/2012
 
006 ( 30) OUTLET BOXES ARE NOT SECURED
ROOF: A/C UNIT
RSLV 12/09/2011 12/09/2011 02/09/2012
 
007 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BSMT: GROUND RACEWAY AT WATER MAIN
RSLV 12/09/2011 12/09/2011 02/09/2012
 
008 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
BSMT: SER SWITCHES NOT GROUP
RSLV 02/09/2012 02/09/2012 07/19/2012
 
009 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BSMT: WATER METER NOT JUMP
RSLV 02/09/2012 02/09/2012 07/19/2012
 
010 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BSMT: FUSE CUT OUT BOX RACEWAY NOT BONDED
RSLV 02/09/2012 02/09/2012 07/19/2012