BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M309747
Premises: 431 WEST 37 STREET MANHATTAN BIN: 1088683     Block: 735   Lot: 17
   
Application Completed and Certified

Filed: 431 W 37TH ST Census Tract:   1110 Health Area:  5500
CELLAR - 12TH FLOOR, ROOF Admin Area:   M - MANHATTAN Inspection Area:   Q
NEW YORK, NY 10018 Community Board:   104
Related Job Number:    110220289
DOB Cross Street(s):   DYER AVENUE,    10 AVENUE
Status:   C - JOB IS SIGNED OFF 08/21/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/15/2010 6:17 PM
Application Entered:   12/15/2010 Job Start Date:   12/16/2010
Last Change:   08/21/2013 Job End Date:   12/16/2012
Appointment Status:   
Last Inspection By:   BEST, J       On     09/21/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011735 Licensee Name: YITZHAK ADIKA
Firm: 003323 Firm Name: I.K.E. ELECTRICAL CORP.
Firm Phone: 212-444-2558  Firm Address: 601 WEST 26TH ST.,SUITE 1695 NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval # / Submittal #:   
Owner / Occup: AMNON SHALHOV
Owner Business Name: JOY CONSTRUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  2-400 AMP
D. 601 Up to 1200 AMPS  1  800 AMP
E. Over 1200 AMPS  2  1- 1200 AMP /1- 2500 AMP
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  100  100 SETS OF #2
B. Over #2 to 1/0  7  7 SETS OF #2 3 PHASE
C. Over 1/0 to 250 MCM  7  7 SETS OF 3/0
D. Over 250 MCM  3  3 SETS OF 600 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  100  100 - 100AMP APT PANEL
C. 3 Phase Up to 225 AMPS  12  5-200 AMP / 7-100 AMP
D. 3 Phase Over 225 AMPS  3  1-1200 AMP 2-400 AMP
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    100  45    30  100             
001    86  35    25  86             
002    125  85    42  125             
003    75  85    35  75             
004    75  85    35  75             
005    75  85    35  75             
006    75  85    35  75             
007    75  85    35  75             
008    75  85    35  75             
009    75  85    35  75             
010    75  85    35  75             
011    75  85    35  75             
012    75  85    35  75             
TOW              20         
ROF             
Buildings Total 1069  1019    450  1069     26           
Total Units : 3633 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 100 #4-Wire 0 #10-Wire 3
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/15/2010 Notice: 1 - FIRST NOTICE 08/10/2012
Power Issued: 12/15/2010 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M309747
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/26/2012 08/10/2012 GYM V E (375) (7) Y
INSPECTION COMMENTS: NOT A FINAL INSPECTION* INSPECTED ARTS 12A 12D,11C,11A,10F,10E,9A,9E ,7S,7G,6B,5B,5K,4B,4K,2N,2P ONLY
 
(2) 09/21/2012 10/02/2012 JSB C R E (150) (0) Y
INSPECTION COMMENTS: *ELEVATOR FILING REMOVED BY FILING OF APP.#M313839*

OBJECTION FOR APPLICATION #: M309747
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT FIRE PUMP SERV NVV.IS NOT REMOTE 12 INCHES APRT ART 695.4B3
RSLV 07/26/2012 07/26/2012 09/21/2012
 
002 (999) OTHER
BSMT ART.110.26 FIRE RATED DOOR WITH PANIC HARD WARE NOT PROVIDED FOFOR NEVV 250OAMP 1200AM.SERV.SW
RSLV 07/26/2012 07/26/2012 09/21/2012
 
003 (999) OTHER
BSMT DOOR TO BOILER RM 800AMP SER SW FIRE PUMP 400AM DELTA COMBINATIION IS NOT AS PER DWG ART 110.2 CALENDAR#50523 REV 3
RSLV 07/26/2012 07/26/2012 09/21/2012
 
004 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
ALL FLR BEDRD CLST LGTS AND BEDRM LGTS
RSLV 07/26/2012 07/26/2012 09/21/2012
 
005 (999) OTHER
BSMT TAT 310.15 COMMON RISERS IN TROUGH ARE NOT DRATED
RSLV 07/26/2012 07/26/2012 09/21/2012
 
006 (999) OTHER
ALL FLRS ALL AREA WITH MCCABLE BRANCH CIRCUIT WIRIN NOT ALL METALBOXES ARE BONDED ART 250.146 148
RSLV 07/26/2012 07/26/2012 09/21/2012
 
007 (999) OTHER
ALL FLR MC CABLE IS NOT GRDED IN ALL PNLS ART 250.146
RSLV 07/26/2012 07/26/2012 09/21/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back