Electrical Application Details for App #: M309457
Premises: 528 WEST BROADWAY MANHATTAN BIN: 1008644     Block: 537   Lot: 30
   
Application Completed and Certified

Filed: 530 LAGUARDIA PL Census Tract:   6500 Health Area:  5700
2ND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   BLEECKER STREET,    WEST 3 STREET
Status:   C - JOB IS SIGNED OFF 11/20/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/07/2010 10:46 AM
Application Entered:   12/07/2010 Job Start Date:   12/07/2010
Last Change:   11/20/2012 Job End Date:   12/07/2011
Appointment Status:   
Last Inspection By:   RIVERA, F       On     05/30/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009232 Licensee Name: MARTIN DUBBS
Firm: 003844 Firm Name: M & M CONTROL WIRING &
Firm Phone: 718-477-5342  Firm Address: 2952 RICHMOND TERRACE ELECTRICAL, INC STATEN ISLAND NY 10303 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $110.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   E - Four Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SERGEY FRISS
Owner Business Name: CORNERSTONE BUILDERS GRP
Authorized Representative:  SERGEY FRISS
Relationship To Owner:   GC


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002      40    15  30         
Buildings Total   40    15  30              
Total Units : 91 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/09/2012
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M309457
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/18/2011 10/27/2011 CCH A (60) (3) Y
INSPECTION COMMENTS: *ABOUT TEN CEILING FIXTURES MISSING* SEE VIOLATION DETAILS
 
(2) 02/09/2012 02/22/2012 CCH A R (60) (2) Y
INSPECTION COMMENTS: SEE VIOLTION DETAILS
 
(3) 05/24/2012 06/09/2012 CCH A R (45) (1) Y
INSPECTION COMMENTS: *NEED TO REMOVE OVEN TO CHECK WIRE FROM PANEL* SEE VIOLATION DETAILS
 
(4) 05/30/2012 06/12/2012 FRI C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M309457
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
PANELS: PANEL DIRECTORY
RSLV 10/18/2011 10/18/2011 02/09/2012
 
002 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
M/BED: OUTLET NOT ARC FAULT
RSLV 10/18/2011 10/18/2011 02/09/2012
 
003 (999) OTHER
PANELS: GREEN WIRE AS PHASE.....RECERTIFIED..... - 250.119*NOT A FINAL*
RSLV 10/18/2011 10/18/2011 02/09/2012
 
004 ( 17) DEFECTIVE SWITCHES ARE IN USE
PANEL: DEF ARC FAULT BREAKER FOR MASTER BEDROOM
RSLV 02/09/2012 02/09/2012 05/24/2012
 
005 (999) OTHER
KITCHEN: GREEN WIRE AS PHASE #10 FOR OVEN........ - 250.119
RSLV 02/09/2012 02/09/2012 05/24/2012
 
006 (999) OTHER
KITCHEN: GREENWIRE AS PHASE #10 FOR OVEN...... - 250.119
RSLV 05/24/2012 05/24/2012 05/30/2012