Electrical Application Details for App #: M309306
Premises: 101 NORFOLK STREET MANHATTAN BIN: 1079376     Block: 353   Lot: 40
   
Application Completed and Certified

Filed: 101 NORFOLK ST Census Tract:   1800 Health Area:  7400
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   V
NEW YORK, NY 10002 Community Board:   103
DOB Cross Street(s):   DELANCEY STREET,    RIVINGTON STREET
Status:   C - JOB IS SIGNED OFF 02/24/2011
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/01/2010 2:09 PM
Application Entered:   12/01/2010 Job Start Date:   12/01/2010
Last Change:   02/24/2011 Job End Date:   12/02/2011
Appointment Status:   
Last Inspection By:   MCKENZIE, W.       On     02/22/2011      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012022 Licensee Name: JOSEPH SORTINO
Firm: 003742 Firm Name: TOP SHELF ELECTRIC CORP
Firm Phone: 718-815-1700  Firm Address: 3917 AMBOY ROAD STATEN ISLAND NY 10308 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $785.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PAUL RHEELING
Owner Business Name: ON THE LEVEL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400
D. 601 Up to 1200 AMPS  1  1200SW FUSE 601
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  2 SETS 3/0 FEEDERS
D. Over 250 MCM  2  2 SETS 500
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  1-200A COMBO PLP;1-200A
D. 3 Phase Over 225 AMPS  1  1-400A PANEL
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 3 #10-Wire 1
Existing Meters 0 + New Meters 4 - Removed Meters 0 = Total Meters 4

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/01/2010 Notice: 1 - FIRST NOTICE 01/14/2011
Power Issued: 12/01/2010 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M309306
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/07/2011 01/14/2011 CCH A G (45) (5) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 02/22/2011 02/24/2011 WMK C R E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M309306
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
A) SER ROOM: 1200A SER SW NEUTRAL NOT BONDED.... - 250.28
RSLV 01/07/2011 01/07/2011 02/22/2011
 
002 (999) OTHER
B) ALL DIS SWS NEUTRAL BONDED AFTER SER SW... - 250.24.A.5
RSLV 01/07/2011 01/07/2011 02/22/2011
 
003 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
A) 2ND FLOOR: 2ND FLOOR PANEL
RSLV 01/07/2011 01/07/2011 02/22/2011
 
004 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
THROUGH-OUT: 30A BREAKER ON #12 WIRE
RSLV 01/07/2011 01/07/2011 02/22/2011
 
005 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
B) MECH.ROOM: 200A DIS SW
RSLV 01/07/2011 01/07/2011 02/22/2011