BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M308553
Premises: 160 ORCHARD STREET MANHATTAN BIN: 1077189     Block: 411   Lot: 8
   
Application Completed and Certified

Filed: 160 ORCHARD ST Census Tract:   30.01 Health Area:  6600
BASEMENT & APARTMENT 6-F Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10002 Community Board:   103
DOB Cross Street(s):   RIVINGTON STREET,    STANTON STREET
Status:   C - JOB IS SIGNED OFF 07/07/2011
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/08/2010 9:55 AM
Application Entered:   11/08/2010 Job Start Date:   11/08/2010
Last Change:   07/07/2011 Job End Date:   02/08/2011
Appointment Status:   
Last Inspection By:   BEST, J       On     06/23/2011      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010606 Licensee Name: MYRON COHEN
Firm: 003435 Firm Name: A.T. ELEC'L CONTR'G, INC
Firm Phone: 718-234-9250  Firm Address: 1561 64TH STREET BROOKLYN NY 11219 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $212.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (2  Stores, 8 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SION MISRAHI
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  #500MCM
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  #6/3 WIRE
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  3  #2/4 WIRE
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004  6-F  20             
Buildings Total 20                
Total Units : 41 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 9 #4-Wire 2 #10-Wire 0
Existing Meters 10 + New Meters 11 - Removed Meters 10 = Total Meters 11

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/08/2010 Notice: 1 - FIRST NOTICE 05/10/2011
Power Issued: 11/08/2010 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M308553
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/03/2011 05/10/2011 CLC A E (45) (5) Y
INSPECTION COMMENTS: N/A
 
(2) 06/23/2011 06/30/2011 JSB C R E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M308553
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
APT 6F- BEDROOM LIGHT NOE AFCI PROTECTION 210.12B
RSLV 05/03/2011 05/03/2011 06/23/2011
 
002 (999) OTHER
APT 6F- ENTIRE OUTLET NOT GROUNDED 250.146
RSLV 05/03/2011 05/03/2011 06/23/2011
 
003 ( 19) DEFECTIVE WIRING IS IN USE
APT 6F- KITCHEN UNDER CABINET LIGHTING ROMOX IN USES
RSLV 05/03/2011 05/03/2011 06/23/2011
 
004 (999) OTHER
BSMT- CEILING FEEDERS SPLICE BOX NOT ACCESSIBLE 300.15
RSLV 05/03/2011 05/03/2011 06/23/2011
 
005 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
BSMT- APT FEEDER IN 2IN RACEWAY 15 CONDUCTOR HAVE NOT BEEN DERATED
RSLV 05/03/2011 05/03/2011 06/23/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.