BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M307124
Premises: 692 BROADWAY MANHATTAN BIN: 1008529     Block: 531   Lot: 7501
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 692 BROADWAY Census Tract:   55.02 Health Area:  5700
2 Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   GREAT JONES STREET,    EAST 4 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/24/2010 11:34 AM
Application Entered:   09/24/2010 Job Start Date:   09/24/2010
Last Change:   08/22/2025 Job End Date:   09/23/2011
Appointment Status:   
Last Inspection By:   MCKENZIE, W.       On     02/10/2011      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  B - CANCEL POWER AUTH
Objection Disposition:  X - NOT REMOVED

License #: 012022 Licensee Name: JOSEPH SORTINO
Firm: 003742 Firm Name: TOP SHELF ELECTRIC CORP
Firm Phone: 718-815-1700  Firm Address: 3917 AMBOY ROAD STATEN ISLAND NY 10308 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $1,032.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Other
Store / Other:   GYM
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: FITNESS BLINK
Owner Business Name: OWNER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  0
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  4  2 SETS OF 400MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  6  3 PANELS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002    300  52    15  300  12         
Buildings Total 300  52    15  300     12           
Total Units : 679 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: K - CANCELLED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: C - CALL TO OFFICE 03/31/2011
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M307124
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/10/2011 03/01/2011 WMK V B (62) (3) Y
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(2) 02/10/2011 03/01/2011 WMK A X B (62) (0) Y
INSPECTION COMMENTS: No Inspection Comments For This Application

OBJECTION FOR APPLICATION #: M307124
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (129) SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE
Basement Service Room
OPEN 02/10/2011 02/10/2011
 
002 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
Installed second fusing to one of the existing 600 amps ServiceSwitch.in Basement
OPEN 02/10/2011 02/10/2011
 
003 (999) OTHER
(Art 250.28) Grounded conductor not provided in existing ServiceSwitch is reused .Also Fire Alarm Fuse Cut-Out Neutral not to Encl.:Basement
OPEN 02/10/2011 02/10/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back