BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M306533
Premises: 34 WEST 14 STREET MANHATTAN BIN: 1009713     Block: 577   Lot: 19
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 34 W 14 ST Census Tract:   6300 Health Area:  5700
4-FL, ROOF Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):    5 AVENUE,    AVENUE OF THE AMERICAS
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/06/2010 7:33 PM
Application Entered:   09/06/2010 Job Start Date:   09/06/2010
Last Change:   08/22/2025 Job End Date:   09/05/2011
Appointment Status:   
Last Inspection By:   FAY, RICHARD       On     10/18/2012      
Field Disp:   N - NO ACCESS
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 011756 Licensee Name: LEONID SIMKIN
Firm: 003366 Firm Name: LENS ELECTRIC, INC
Firm Phone: 646-522-7311  Firm Address: 2802 AVENUE Y BROOKLYN NY 11235 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $107.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ARJAN MUSEIJANI
Owner Business Name: A&B CONSTRUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  1 SET #2AWG,#4 W #6 GROUD
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  1 100AMP PANEL
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004                 
ROF                     
Buildings Total          15           
Total Units : 19 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 08/07/2012
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M306533
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/03/2011 11/15/2011 CCH N (60) (0) Y
INSPECTION COMMENTS: NO SHOW - NO ACCESS
 
(2) 03/08/2012 03/19/2012 CCH V (60) (6) Y
INSPECTION COMMENTS: *CHECK DRAWING IF LIGHT INSTALLED PANEL AND FEEDERS* SEE VIOLATION DETAILS
 
(3) 06/11/2012 06/20/2012 JSV N (10) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR AND STATED NOT AWARE OF APPOINTMENT
 
(4) 07/19/2012 08/07/2012 LBI V Y (70) (6) Y
INSPECTION COMMENTS: DID NOT CHECK 40AMP AIR HANDLER LADIES LOCKER ROOM CEILING
 
(5) 10/18/2012 11/09/2012 RFY N (20) (0) Y
INSPECTION COMMENTS: *CALLED CONTRACTOR - INFORMED ME THAT HE NEVER RECEIVED NOTIFICATION OF INSPECTION*

OBJECTION FOR APPLICATION #: M306533
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
A) CEILING: DEF WIRING IN TROUGH NEUTRAL TO GROUND
OPEN 03/08/2012 07/19/2012
 
002 ( 19) DEFECTIVE WIRING IS IN USE
B) PANEL: TWO WIRES UNDER ONE BREAKER
RSLV 03/08/2012 03/08/2012 07/19/2012
 
003 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
PANEL: NO GROUND DIR:
OPEN 03/08/2012 07/19/2012
 
004 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
PANEL: BLANKS MISSING
RSLV 03/08/2012 03/08/2012 07/19/2012
 
005 (999) OTHER
THROUGH-OUT: OUTLET NOT BONDED...... - 250.146
RSLV 03/08/2012 03/08/2012 07/19/2012
 
006 ( 19) DEFECTIVE WIRING IS IN USE
C) LOCKER ROOML NO GREEN WIRE IN GREENFIELD TO 220V OUTLET(CEILING)*NOT FINAL*
OPEN 03/08/2012 07/19/2012
 
007 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
ENTIRE WHITE WIRE TAPED GREEN IN VSE THROUGHOUT 250.119
OPEN 07/19/2012 07/19/2012
 
008 (999) OTHER
CEILING 220V RECEPTACLE BOX IS NOT GROUNDED (LOCKER ROOM) 314.4
OPEN 07/19/2012 07/19/2012
 
009 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ROOF A/C DISCONNECT ENCLOSURE NOT BONDED
OPEN 07/19/2012 07/19/2012
 
010 (999) OTHER
DANCE ROOM ECESSIVE GAP AROUND RECEPTACLE BOX COVER 314.21
OPEN 07/19/2012 07/19/2012
 
011 ( 30) OUTLET BOXES ARE NOT SECURED
DANCE ROOM RECEPTACLE LOOSE IN BALLET ROOM
OPEN 07/19/2012 07/19/2012
 
012 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
PANEL WHITE WIRE IN USE AS HOT
OPEN 07/19/2012 07/19/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back