Electrical Application Details for App #: M306379
Premises: 250 WEST 24 STREET MANHATTAN BIN: 1084993     Block: 773   Lot: 12
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 250 W 24TH ST. Census Tract:   9100 Health Area:  5200
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10011 Community Board:   104
Special Place Name:   CHELSEA GARDENS
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   C - JOB IS SIGNED OFF 08/25/2016 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/01/2010 9:52 AM
Application Entered:   09/01/2010 Job Start Date:   09/03/2010
Last Change:   08/25/2016 Job End Date:   03/06/2011
Appointment Status:   
Last Inspection By:   MCPARTLAND, BRIAN       On     08/03/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  R - REMOVED

License #: 009313 Licensee Name: JAMES VOLPE
Firm: 002025 Firm Name: HI-TECH ELECTRIC INC
Firm Phone: 718-984-3393  Firm Address: 567 MIDLAND AVENUE STATEN ISLAND NY 10306 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $676.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PAUL FAGLIONE
Owner Business Name: MARLITE CONSTRUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  3PHASE 600A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  
B. Over #2 to 1/0  5  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  6  1PHASE 220V 12/24/ EACH
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  3PHASE 220V 30CIR/ EACH
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS  B1-E               
BAS  B1-W  52  35  18  52             
BAS  B2-E  10  20  10             
BAS  B2-W  14  22  14             
BAS  B3-E  17  20             
Buildings Total 90  103  28  44  90                
Total Units : 355 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/01/2010 Notice: 1 - FIRST NOTICE 05/29/2015
Power Issued: 09/01/2010 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M306379
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/22/2015 05/29/2015 NRS V G (260) (24) Y
INSPECTION COMMENTS: B1E IS IN BASEMENT AREA OF BAE,B2-3 IS NOW GBE.B3-E IS NOW GCE AFCIS NOT CHECKED,NO PANEL SCHEDULE
 
(2) 08/03/2016 08/04/2016 BMP C R (50) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED. CERTIFIED.

OBJECTION FOR APPLICATION #: M306379
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(ALL FLOORS) EL.ROOM: TROUGH ABOVE METER
RSLV 05/22/2015 05/22/2015 08/03/2016
 
002 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(ALL FLOORS) EL ROOM
RSLV 05/22/2015 05/22/2015 08/03/2016
 
003 (999) OTHER
(ALL FLOORS) EL ROOM: BOTH TROUGH NOT SECURED 4'X 6' X 6".. 376.30
RSLV 05/22/2015 05/22/2015 08/03/2016
 
004 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ALL FLOORS)EL.ROOM: TROUGH BOTH 6" X 6" X 4'(MAX CABLE SIZE 500 MCM)
RSLV 05/22/2015 05/22/2015 08/03/2016
 
005 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(ALL FLOORS) BASE: WATER GR.CLAMP & LUG ARE LOOSE
RSLV 05/22/2015 05/22/2015 08/03/2016
 
006 (999) OTHER
(ALL FLOORS) BASE: WATER GR CLAMP DOUBLE LUGGED.. 110.14
RSLV 05/22/2015 05/22/2015 08/03/2016
 
007 (279) WATER METER JUMPER IS MISSING/IMPROPER
(ALL FLOORS) BASE: UNDERSIZED
RSLV 05/22/2015 05/22/2015 08/03/2016
 
008 (999) OTHER
(ALL FLOORS) OUTSIDE: SUPPLEMENTAL GROUND ROD NEXT TO WALL.. 250.56
RSLV 05/22/2015 05/22/2015 08/03/2016
 
009 (999) OTHER
(ALL FLOORS)EL.ROOM: TAP ON TAP IN METER TERMINAL BOX 600 TO 3/0 TO #3 AWG260.21
RSLV 05/22/2015 05/22/2015 08/03/2016
 
010 (999) OTHER
(ALL FLOORS)EL ROOM:2' X 4" X 4" & 4' X 6" X " TROUGHS NOT SIZED AS PER 376.23
RSLV 05/22/2015 05/22/2015 08/03/2016
 
011 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
(ALL FLOORS) BASE: PLP WEST & PLP EAST
RSLV 05/22/2015 05/22/2015 08/03/2016
 
012 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(ALL FLOORS) BASE: PLP WEST & PLP - EAST
RSLV 05/22/2015 05/22/2015 08/03/2016
 
013 (999) OTHER
(ALL FLOORS) BASE: G.F.C.I.UNDER PLP W NOT MOUNTED AS PER 406.4(C)
RSLV 05/22/2015 05/22/2015 08/03/2016
 
014 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(ALL FLOORS) BASE: B2-W,B1-W
RSLV 05/22/2015 05/22/2015 08/03/2016
 
015 (999) OTHER
(ALL FLOORS)BASE: B2-W BEDR.RECE AT BOTTOM BUILT IN SHELVS NEXT TO DESK & M.WSET TOO DDEP.. 314.20
RSLV 05/22/2015 05/22/2015 08/03/2016
 
016 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(ALL FLOORS) B1-W: COUNTER G.F.C.I.ON THE RIGHT OF STOVE
RSLV 05/22/2015 05/22/2015 08/03/2016
 
017 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(ALL FLOORS) B1-W: #14 AWG E.B.J.USED IN OUTLET BOXES
RSLV 05/22/2015 05/22/2015 08/03/2016
 
018 ( 27) ARMORED CABLES INSTALLED WITHOUT INSULATING BUSHINGS
(ALL FLOORS) B1-W: BATHROOM
RSLV 05/22/2015 05/22/2015 08/03/2016
 
019 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
(ALL FLOORS) BASE: PLP E
RSLV 05/22/2015 05/22/2015 08/03/2016
 
020 ( 19) DEFECTIVE WIRING IS IN USE
(ALL FLOORS) BASE: PLP E #14 AWG WIRE USED.. 210.24 AM
RSLV 05/22/2015 05/22/2015 08/03/2016
 
021 (999) OTHER
(ALL FLOORS) BASE: BREAKER DOUBLE LUGGED IN PLP-E.. 110.14
RSLV 05/22/2015 05/22/2015 08/03/2016
 
022 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(ALL FLOORS) BASE: APT.GAE
RSLV 05/22/2015 05/22/2015 08/03/2016
 
023 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(ALL FLOORS) BASE: GAE A/C COMP E.B.J.NOT PER 250.122
RSLV 05/22/2015 05/22/2015 08/03/2016
 
024 (999) OTHER
(ALL FLOORS) BASE: GAE A/C LFMC OVER 6'.. 350.12(3)AM
RSLV 05/22/2015 05/22/2015 08/03/2016