BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M306037
Premises: 300 ALBANY STREET MANHATTAN BIN: 1000436     Block: 16   Lot: 7504
   
Application Completed and Certified

Filed: 300 ALBANY ST Census Tract:   317.01 Health Area:  8900
GROUND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10280 Community Board:   101
Special Place Name:   HUDSON PRODUCE INC.
DOB Cross Street(s):   SOUTH END AVENUE,    DEAD END
Status:   C - JOB IS SIGNED OFF 03/14/2011
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/24/2010 5:45 PM
Application Entered:   08/24/2010 Job Start Date:   08/30/2010
Last Change:   03/14/2011 Job End Date:   08/20/2011
Appointment Status:   
Last Inspection By:   HINDS EUGENE       On     02/16/2011      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  R - REMOVED

License #: 012015 Licensee Name: MIECZYSLAW KARDASZ
Firm: 003926 Firm Name: MK ELECTRIC CONTR'S, INC
Firm Phone: 718-646-0128  Firm Address: 10 BAY 22ND STREET BROOKLYN NY 11214 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $167.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (6  Stores, 40 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JAMES KIM
Owner Business Name: HUDSON PRODUCE INC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  4#3/0
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  200 AMPS, 42CKTS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    60  20    20  60  10  40         
Buildings Total 60  20    20  60     40           
Total Units : 200 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  12/13/2010
Power Issued: Response: V - OBJ WAS REMOVED 01/14/2011

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M306037
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/07/2010 12/13/2010 WMK A G (30) (1) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 02/16/2011 02/24/2011 EHD C R (45) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M306037
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
STORE PANEL: MORE THAN THREE CURRENT CARRING CONDUCTORS INSIDE E.M.TNOT DERATED - IMPROPER FUSING........ - ART.310.15(B)(2)(4)
RSLV 12/07/2010 12/07/2010 02/16/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order