BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M305597
Premises: 648 BROADWAY MANHATTAN BIN: 1008419     Block: 529   Lot: 3
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 648 BROADWAY Census Tract:   55.02 Health Area:  5700
2 THRU 10 Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   BLEECKER STREET,    BOND STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/11/2010 4:43 AM
Application Entered:   08/11/2010 Job Start Date:   08/12/2010
Last Change:   08/22/2025 Job End Date:   09/20/2010
Appointment Status:   
Last Inspection By:   MARCIN DUBAJ       On     04/23/2018      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 010482 Licensee Name: HARVEY ISAACMAN
Firm: 002810 Firm Name: ELECTRICAL SOLUTIONS LLC
Firm Phone: 718-788-2018  Firm Address: 145 30TH STREET BROOKLYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
7 - HVAC WIRING
Total Fee:  $206.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PERRY PARKER
Owner Business Name: SIERRA REALITY CORP.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  100 AMP THREE PHASE
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  12 /24 CR.
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 2 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 08/11/2010 Notice: 1 - FIRST NOTICE 04/23/2018
Power Issued: 08/11/2010 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M305597
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/01/2016 11/02/2016 PHG J (20) (0) Y
INSPECTION COMMENTS: CONTRACTOR TO FIX APP TO REFLECT JOB
 
(2) 04/23/2018 04/23/2018 MJD V (35) (4)
INSPECTION COMMENTS: FAIL.

OBJECTION FOR APPLICATION #: M305597
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ROOF) A/C DISCONNECT SWITCH USED AS RACEWAY ART. 312.8
OPEN 04/23/2018 04/23/2018
 
002 (999) OTHER
(ROOF) ELECTRICAL BOX NOT SUPPORTED ART. 314.23
OPEN 04/23/2018 04/23/2018
 
003 (999) OTHER
(ROOF) CONDUIT NOT SUPPORTED ART. 342.30
OPEN 04/23/2018 04/23/2018
 
004 (999) OTHER
(ROOF) SERVICING RECEPTACLE FOR A/C UNIT NOT PROVIDED ART. 210.63
OPEN 04/23/2018 04/23/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.