BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M305275
Premises: 26 EAST 91 STREET MANHATTAN BIN: 1047004     Block: 1502   Lot: 56
   
Application Completed and Certified

Filed: 26 E 91 ST Census Tract:   150.02 Health Area:  3600
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10128 Community Board:   108
DOB Cross Street(s):    5 AVENUE,    MADISON AVENUE
Status:   C - JOB IS SIGNED OFF 01/11/2011
Request Type:   P - PICK-UP eFiled:   YES
Application Entered:   11/29/2010 Job Start Date:   11/29/2010
Last Change:   01/11/2011 Job End Date:   11/30/2010
Appointment Status:   
Last Inspection By:   BEST, J       On     01/06/2011      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011690 Licensee Name: ARISTEDES FOTAKOS
Firm: 001971 Firm Name: ATHENS ELECTRIC INC.
Firm Phone: 718-234-9193  Firm Address: 1980 63RD STREET BROOKLYN NY 11204 

Other Licensees and Firms:
License # Licensee Name Firm # Firm Name Type
010738 FOTAKOS, GEORGE 001971 ATHENS ELECTRIC INC. RESPONSIBLE REP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $40.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Other
Store / Other:   BSMT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JANE GOLDMAN
Owner Business Name: SOLIL MANAGEMENT CORP
Authorized Representative:  LOUISA LITTLE
Relationship To Owner:   BLDG REP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                       
Buildings Total                       
Total Units : 1 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/11/2011 Notice:  08/02/2010
Power Issued: 01/11/2011 Response: F - FILED TO REMOVE OBJECTION 11/29/2010

Follow-Up: X - FILED APPL,NOW CLOSED 11/29/2010
Contractor's Comments:  INSTALLED NEW GROUND TO 600A SERVICE SWITCH AND BOND ACCORDINGLY.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M305275
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/23/2010 08/02/2010 NEI W (5) (2)
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 01/06/2011 01/11/2011 JSB C R E (45) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M305275
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
NEUTRAL IS BONDED AFTER SER SW.........250.24 A5
RSLV 07/23/2010 07/23/2010 01/06/2011
 
002 (999) OTHER
GROUNDING SHALL NOT BE INSTALLED AFTER SER SW.......250.24 A5*600A DISCONNECT WHICH WAS A SER SW*
RSLV 07/23/2010 07/23/2010 01/06/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.