BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M304867
Premises: 436 EAST 13 STREET MANHATTAN BIN: 1090881     Block: 440   Lot: 26
   
Application Completed and Certified

Filed: 436 E 13 ST Census Tract:   34 Health Area:  6200
2ND FL,APT 1,APT 2 Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10009 Community Board:   103
DOB Cross Street(s):    1 AVENUE,    AVENUE A
Status:   C - JOB IS SIGNED OFF 03/24/2011
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   07/21/2010 Job Start Date:   07/12/2010
Last Change:   03/24/2011 Job End Date:   07/30/2010
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     02/07/2011      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009335 Licensee Name: PAUL L QUANTANO
Firm: 000470 Firm Name: ELEC'L MOTOR MAINT. INC.
Firm Phone: 917-601-1912  Firm Address: 330 7 AVE 18 FLOOR SUITE 801 NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $91.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: ELECTRICAL MOTOR MAINTEAN
Authorized Representative:  PAUL QUANTANO
Relationship To Owner:   X


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002  10               
002  10               
Buildings Total 20                  
Total Units : 36 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 2 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/21/2010 Notice: 1 - FIRST NOTICE 02/03/2011
Power Issued: 07/21/2010 Response: V - OBJ WAS REMOVED 01/19/2011

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M304867
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/02/2010 12/09/2010 DAH A E (20) (3) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 01/28/2011 02/03/2011 CCH A R E (30) (1) Y
INSPECTION COMMENTS: NONE
 
(3) 02/07/2011 02/10/2011 DAH C R E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M304867
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
GARAGE: NEUTRAL BONDED AFTER SVC2-100A CKT BKR PANEL
RSLV 12/02/2010 12/02/2010 01/28/2011
 
002 (999) OTHER
GARAGE: JUMPER NOT PROVIDED...... - 250
RSLV 12/02/2010 12/02/2010 01/28/2011
 
003 (999) OTHER
GARAGE: KO AT FDR RACEWAY NOT MECHANICALLY BONDED..... - 250*NOT A FINAL*
RSLV 12/02/2010 12/02/2010 01/28/2011
 
004 (999) OTHER
GARAGE 400A SER SW NEUTRAL NOT BONDED 250.28
RSLV 01/28/2011 01/28/2011 02/07/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order