BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M301248
Premises: 99 CHAMBERS STREET MANHATTAN BIN: 1001631     Block: 149   Lot: 14
   
Application Completed and Certified

Filed: 165 CHURCH ST Census Tract:   21 Health Area:  7700
BASEMENT SERVICE AREA Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10007 Community Board:   101
DOB Cross Street(s):   CHAMBERS STREET,    READE STREET
Status:   C - JOB IS SIGNED OFF 06/07/2011
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/30/2010 7:12 AM
Application Entered:   03/30/2010 Job Start Date:   03/31/2010
Last Change:   06/07/2011 Job End Date:   02/28/2011
Appointment Status:   
Last Inspection By:   DALTON HENLON       On     04/05/2011      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010851 Licensee Name: RONALD J TESTA, JR.
Firm: 001416 Firm Name: TESTA ELECTRIC CO., INC
Firm Phone: 718-331-2747  Firm Address: 1435 65TH STREET, 2ND FL BROOKLYN NY 11219 

Other Licensees and Firms:
License # Licensee Name Firm # Firm Name Type
009514 TESTA, RONALD 001416 TESTA ELECTRIC CO., INC RESPONSIBLE REP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $535.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (6  Stores, 8 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: TRANSWORLD EQUITIES CO
Authorized Representative:  DAN ADLER
Relationship To Owner:   PM


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  400 AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  3  3/0
D. Over 250 MCM  2  SETS OF 500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 8 #10-Wire 0
Existing Meters 14 + New Meters 8 - Removed Meters 8 = Total Meters 14

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/30/2010 Notice: C - CALL TO OFFICE 02/01/2011
Power Issued: 03/30/2010 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW SERVICE EQUIPMENT. PICK UP EXISTING LOADS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M301248
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/06/2010 10/15/2010 DAH A G (45) (2) Y
INSPECTION COMMENTS: *TERMINATION AT WATER MAIN IS INACCESSIBLE - TROUGH NOT INSPECTED* SEE VIOLATION DETAILS
 
(2) 01/24/2011 02/01/2011 RPL H X E (30) (0) Y
INSPECTION COMMENTS: NONE
 
(3) 04/05/2011 04/11/2011 DAH C R E (25) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M301248
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT: JUMPER IS NOT PROVIDED........ - 250.53D400A FDR TERMINAL
RSLV 10/06/2010 01/24/2011 04/05/2011
 
002 (999) OTHER
BSMT: SUPP;EMENTAL GROUND NOT INSTALLED..... - 250.50*NOT A FINAL*
RSLV 10/06/2010 01/24/2011 04/05/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back