| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
1 |
|
| E. Over 1200 AMPS |
1 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
5 |
5/4#2 -1 #8=1.25" |
| B. Over #2 to 1/0 |
2 |
1/4 #1/0 1#6-2", 1/4 #1-1 |
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
16 |
4/4#350MCM 1#1 4", 8/4 50 |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
3 |
|
| D. 3 Phase Over 225 AMPS |
2 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
1 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 4) |
SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL 2ND FL: SVC OVER 1000 JVA NO ADVISORY BOARD APPROVAL |
RSLV |
07/19/2013 |
07/19/2013 |
09/03/2013 |
| |
| 002 |
(999) |
OTHER 2ND FL: SVC RM EGRESS DOES NOT OPEN OUT.... - 110.26 |
RSLV |
07/19/2013 |
07/19/2013 |
09/03/2013 |
| |
| 003 |
(999) |
OTHER 2ND FL: SVC RM EGRESS NOT EQUIPPPED WITH PANIC BARS.... - 110.2C |
RSLV |
07/19/2013 |
07/19/2013 |
09/03/2013 |
| |
| 004 |
(999) |
OTHER 2ND FL: 200 AMP SVC SW NEUTRAL NOT PROVIDED.... - 250.24.C |
RSLV |
07/19/2013 |
07/19/2013 |
09/03/2013 |
| |
| 005 |
(999) |
OTHER 2ND FL: 200 AMP SVC SW NEUTRAL NOT BONDED..... - 250.24B |
RSLV |
07/19/2013 |
07/19/2013 |
09/03/2013 |
| |
| 006 |
(999) |
OTHER 2ND FL: DIS CONN LINK NOT PROVIDED FOR 2800 SVC BUS |
RSLV |
07/19/2013 |
07/19/2013 |
09/03/2013 |
| |
| 007 |
(999) |
OTHER 2ND FL: BONDING JUMPER NOT PROVIDED IN SW GEAR... - 250.24A |
RSLV |
07/19/2013 |
07/19/2013 |
09/03/2013 |
| |
| 008 |
(999) |
OTHER 2ND FL: ARC FLASH LABEL NOT PROVIDED ON EQUIPMENT |
RSLV |
07/19/2013 |
07/19/2013 |
09/03/2013 |
| |
| 009 |
(999) |
OTHER 2ND FL: 1200 AMP FEEDER E.G.C.UNDER SIZE..... - 250.122 |
RSLV |
07/19/2013 |
07/19/2013 |
09/03/2013 |
| |
| 010 |
(999) |
OTHER 2ND FL: SUPPLEMENTAL GROUND NOT PROVIDED TO BLDG STEEL |
RSLV |
07/19/2013 |
07/19/2013 |
09/03/2013 |