BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M299017
Premises: 64 5 AVENUE MANHATTAN BIN: 1009619     Block: 576   Lot: 42
   
Application Completed and Certified

Filed: 66 5 AV Census Tract:   63 Health Area:  5700
302 & 303 Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):   EAST 12 STREET,    EAST 13 STREET
Status:   C - JOB IS SIGNED OFF 06/19/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/07/2010 12:13 PM
Application Entered:   01/07/2010 Job Start Date:   01/07/2010
Last Change:   06/19/2012 Job End Date:   01/14/2010
Appointment Status:   
Last Inspection By:   CHARLES COURTNEY       On     06/11/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009873 Licensee Name: JOE MIDDLETON
Firm: 001933 Firm Name: NORWAY ELECTRIC CORP.
Firm Phone: 718-992-5500  Firm Address: 1205 JEROME AVENUE BRONX NY 10452 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $45.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: TIM SHELDON
Owner Business Name: THE NEW SCHOOL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003      32                   
Buildings Total   32                      
Total Units : 32 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 09/29/2011
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M299017
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/24/2011 06/01/2011 CCH A (60) (4) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 09/22/2011 09/29/2011 CCH H X (60) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(3) 02/02/2012 05/04/2012 CCH Z (0) (0) Y
INSPECTION COMMENTS: NONE
 
(4) 06/11/2012 06/19/2012 CCH C R (45) (0) Y
INSPECTION COMMENTS: X

OBJECTION FOR APPLICATION #: M299017
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
A) 3RD FLOOR: NO GROUNDING WIRE INSTALLED..... - 250.146
RSLV 05/24/2011 09/22/2011 06/11/2012
 
002 (999) OTHER
B) 3RD FLOOR: NO SCREW AND NUTS USED ON OUTLET PLATE... - 406-4C
RSLV 05/24/2011 09/22/2011 06/11/2012
 
003 ( 10) BRANCH CIRCUIT CONDUCTORS ARE NOT PROPER SIZE
3RD FLOOR: NEUTRAL UNDER SIZE (5 CIR PER NEUTRAL)
RSLV 05/24/2011 09/22/2011 06/11/2012
 
004 ( 9) SQ AREA OF SUM OF CONDUCTORS EXCEEDS SQ AREA FILL OF RACEWAY
3RD FLOOR: AMT WIRE IN RACEWAY
RSLV 05/24/2011 09/22/2011 06/11/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back