BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M296846
Premises: 201 WEST 11 STREET MANHATTAN BIN: 1010989     Block: 614   Lot: 61
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 77 GREENWICH AV Census Tract:   77 Health Area:  6100
|ST FLOOR & BSMT. Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):    7 AVENUE,    BANK STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/12/2009 4:27 PM
Application Entered:   10/12/2009 Job Start Date:   10/16/2009
Last Change:   08/22/2025 Job End Date:   10/16/2010
Appointment Status:   
Last Inspection By:   CHARLES COURTNEY       On     09/30/2010      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  B - CANCEL POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010445 Licensee Name: GEORGE MOLLER
Firm: 003016 Firm Name: MOLLER & MOLLER INC.D/B/A
Firm Phone: 718-995-9400  Firm Address: 148-19 GUY R. BREWER BLVD MOLLER & MOLLER ELEC'L C JAMAICA NY 11434 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $213.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   K - Store
Store / Other:   ICE CREAM STORE
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LENZE HELDI
Authorized Representative:  AVIS AVAD
Relationship To Owner:   PRJ. MGR.


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  1 -200A
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  45
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  50
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    15                 
Buildings Total 15                    
Total Units : 23 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: K - CANCELLED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 10/12/2009 Notice: 1 - FIRST NOTICE 10/06/2010
Power Issued: 10/12/2009 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M296846
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/05/2010 04/08/2010 WMK A B (30) (1) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 09/30/2010 10/06/2010 CCH A R B (60) (3) Y
INSPECTION COMMENTS: *NO ACCESS TO WATER GROUND*......... *SEE VIOLATION DETAILS*

OBJECTION FOR APPLICATION #: M296846
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BASEMENT: CONTRACTOR INSTALLED SEVENTH SVC.SEART.230.71(A)
RSLV 04/05/2010 04/05/2010 09/30/2010
 
002 (999) OTHER
A) SER.ROOM: BASEMENT OVER 6 SER SWITCHES....... 230.71A
OPEN 09/30/2010 09/30/2010
 
003 (999) OTHER
B) STORE: NEUTRAL BONDED IN PANEL (GREENWIRE ON N.BAR)...250.24.A5
OPEN 09/30/2010 09/30/2010
 
004 ( 19) DEFECTIVE WIRING IS IN USE
PANEL: TWO CONDUCTORS TAPE TOGETHER FOR BIGGER SIZE WIRE
OPEN 09/30/2010 09/30/2010



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back