| BUILDING OVERVIEW |
Are Feeders Being Installed? : |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER BSMT-ENDLINE BOX DETERIORATED-110-11,12 |
RSLV |
08/12/2009 |
08/12/2009 |
02/03/2011 |
| |
| 002 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY BSMT-SVC END COND TERMINATION NOT VISIBLE-IN CONCRETE |
RSLV |
08/12/2009 |
08/12/2009 |
02/03/2011 |
| |
| 003 |
(999) |
OTHER A)BSMT-USED SVC EQUIP NOT REMOVED 110.12 |
RSLV |
08/12/2009 |
08/12/2009 |
02/03/2011 |
| |
| 004 |
( 37) |
MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED ROOF-EXHAUST FAN-DISCONNECT SW NOT PROVIDED |
RSLV |
08/12/2009 |
08/12/2009 |
02/03/2011 |
| |
| 005 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE APT#-20N PLUG FUSE USED THROUGH-OUT #14AWG |
RSLV |
08/12/2009 |
08/12/2009 |
02/03/2011 |
| |
| 006 |
( 30) |
OUTLET BOXES ARE NOT SECURED #4-OUTLET AT WINDOW-BOX NOT SECURED TO WALL,OPEN GROUND |
RSLV |
08/12/2009 |
08/12/2009 |
02/03/2011 |
| |
| 007 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED #3-EXTENSION CORD PASSING THROUGH OPENING IN WAL IN USE |
RSLV |
08/12/2009 |
08/12/2009 |
02/03/2011 |