BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M295317
Premises: 109 WASHINGTON STREET MANHATTAN BIN: 1001047     Block: 53   Lot: 6
   

Filed: 109 WASHINGTON ST Census Tract:   13 Health Area:  7700
ENTIRE Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10006 Community Board:   101
DOB Cross Street(s):   RECTOR STREET,    CARLISLE STREET
Status:   C - COMPLETED
Request Type:   P - PICK-UP eFiled:   NO
Application Entered:   08/17/2009 Job Start Date:  
Last Change:   02/03/2011 Job End Date:  
Appointment Status:   
Last Inspection By:   SEVERIANO JOHN       On     02/03/2011      
Field Disp:   Q - NO OBJECTION EXISTS
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: Licensee Name: UNKNOWN
Firm: Firm Name: UNKNOWN
Firm Phone:   Firm Address:  

Work Started or Filed by Others: NO
Work Category:    Work To Be Done:   Total Fee:  $0.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Other
Store / Other:   X
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: 109 WASHINGTON STREET LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 08/17/2009
Power Issued: Response:  

Follow-Up: K - (CLOSED) 08/17/2009
Contractor's Comments:  NONE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M295317
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/12/2009 08/17/2009 FRI W (180) (7)
INSPECTION COMMENTS: NONE
 
(2) 02/03/2011 02/03/2011 SVJ Q R (1) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M295317
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT-ENDLINE BOX DETERIORATED-110-11,12
RSLV 08/12/2009 08/12/2009 02/03/2011
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BSMT-SVC END COND TERMINATION NOT VISIBLE-IN CONCRETE
RSLV 08/12/2009 08/12/2009 02/03/2011
 
003 (999) OTHER
A)BSMT-USED SVC EQUIP NOT REMOVED 110.12
RSLV 08/12/2009 08/12/2009 02/03/2011
 
004 ( 37) MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED
ROOF-EXHAUST FAN-DISCONNECT SW NOT PROVIDED
RSLV 08/12/2009 08/12/2009 02/03/2011
 
005 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
APT#-20N PLUG FUSE USED THROUGH-OUT #14AWG
RSLV 08/12/2009 08/12/2009 02/03/2011
 
006 ( 30) OUTLET BOXES ARE NOT SECURED
#4-OUTLET AT WINDOW-BOX NOT SECURED TO WALL,OPEN GROUND
RSLV 08/12/2009 08/12/2009 02/03/2011
 
007 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
#3-EXTENSION CORD PASSING THROUGH OPENING IN WAL IN USE
RSLV 08/12/2009 08/12/2009 02/03/2011