BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M290803
Premises: 84 CLINTON STREET MANHATTAN BIN: 1004198     Block: 348   Lot: 45
   

Filed: 84 CLINTON ST Census Tract:   14.02 Health Area:  7400
? Admin Area:   M - MANHATTAN Inspection Area:   V
NEW YORK, NY 10002 Community Board:   103
Special Place Name:   APARTMENT HOUSE - MULTI DWELLING
DOB Cross Street(s):   RIVINGTON STREET,    DELANCEY STREET
Status:   C - COMPLETED
Request Type:   P - PICK-UP eFiled:   NO
Application Entered:   03/25/2009 Job Start Date:  
Last Change:   04/01/2009 Job End Date:  
Appointment Status:   
Last Inspection By:   REDDINGTON, J.       On     04/01/2009      
Field Disp:   Q - NO OBJECTION EXISTS
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: Licensee Name: UNKNOWN
Firm: Firm Name: UNKNOWN
Firm Phone:   Firm Address:  

Work Started or Filed by Others: NO
Work Category:    Work To Be Done:   Total Fee:  $0.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: HA -LL IVIS NY RLTY CORP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/25/2009
Power Issued: Response:  

Follow-Up: K - (CLOSED) 03/25/2009
Contractor's Comments:  THROUGH-OUT PUBLIC HALLWAYS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M290803
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/23/2009 03/25/2009 SR2 W (30) (1)
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 04/01/2009 04/01/2009 SR2 Q R (1) (0)
INSPECTION COMMENTS: NO VIOLATION EXISTS - RE M283237 (C) (E).....9/7/08

OBJECTION FOR APPLICATION #: M290803
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
NO APPL.ON FILE FOR NEW RINGER (CONDUITS) FROM BSMT THRU-OUT BLDGNEW PULL BOXES ON FLR LANDINGS + FDRS(IN CONDUIT + EMT)INTO ALL APTS
RSLV 03/23/2009 03/23/2009 04/01/2009



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order