BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M290202
Premises: 30 EAST 13 STREET MANHATTAN BIN: 1009384     Block: 570   Lot: 20
   
Application Completed and Certified

Filed: 30 E 13 ST Census Tract:   61 Health Area:  5700
1ST FLOOR Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
DOB Cross Street(s):    5 AVENUE,    UNIVERSITY PLACE
Status:   C - JOB IS SIGNED OFF 06/03/2009
Request Type:   P - PICK-UP eFiled:   YES
Application Entered:   04/06/2009 Job Start Date:   04/10/2009
Last Change:   06/03/2009 Job End Date:   06/10/2009
Appointment Status:   
Last Inspection By:   RIVERA, F       On     05/28/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011716 Licensee Name: JOSEPH D'AMBROSIO
Firm: 003353 Firm Name: ACCURATE ELEC'L CONTR'S C
Firm Phone: 718-668-3220  Firm Address: 680 SHARROTTS ROAD STE 7 (CORP.) STATEN ISLAND NY 10309 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
9 - OTHER
Total Fee:  $40.00
Other Work:   BASEMT ELECTRICAL SER
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Commercial/Residential (1  Stores, 4 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: DOUBLE MK REALTY LLC
Authorized Representative:  KRAUSE MARTY
Relationship To Owner:   MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                       
Buildings Total                       
Total Units : 1 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  03/05/2009
Power Issued: Response: F - FILED TO REMOVE OBJECTION 04/06/2009

Follow-Up: X - FILED APPL,NOW CLOSED 04/06/2009
Contractor's Comments:  REMOVING VIOLATION INSTALLING BONDING WIRES HAD TO PUT DOWN 1 ATT JUST TO SUBMIT APPLICATION. WOULD NOT ACCEPT WITHOUT A WORK OR FLOOR DESCRIPTION. (WE ARE NOT INSTALLING ANDATT) JUST REMOVING VIOLATIONS)

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M290202
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/04/2009 03/05/2009 SVJ W (1) (4)
INSPECTION COMMENTS: *CERTIFIED LETTER SENT FROM CONTRACTOR - RE: M148294*
 
(2) 05/28/2009 06/03/2009 FRI C R (45) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M290202
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
SERV ENT COND
RSLV 03/04/2009 03/04/2009 05/28/2009
 
002 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
SERV ENT E.M.T
RSLV 03/04/2009 03/04/2009 05/28/2009
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
SERV SW NEUTRAL NOT BONDED TO ENCLOSURE
RSLV 03/04/2009 03/04/2009 05/28/2009
 
004 (999) OTHER
SERVICE ENT COND OVER 10' NOT IN 2" CONCRETE
RSLV 03/04/2009 03/04/2009 05/28/2009



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back