BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M288647
Premises: 22 BATTERY PLACE MANHATTAN BIN: 1085492     Block: 16   Lot: 1
   
Application Completed and Certified

Filed: 311 S END AV Census Tract:   317.01 Health Area:  8900
1 FLOOR Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10280 Community Board:   101
Special Place Name:   IZZY & NATS RESTAURANT
DOB Cross Street(s):   ALBANY STREET,    NORTH COVE BIKE PATH
Status:   C - JOB IS SIGNED OFF 05/29/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/13/2009 5:33 PM
Application Entered:   01/13/2009 Job Start Date:   01/14/2009
Last Change:   05/29/2014 Job End Date:   04/20/2009
Appointment Status:   
Last Inspection By:   BEST, J       On     05/20/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010804 Licensee Name: SANG CHEUNG
Firm: 002065 Firm Name: AL-LECTRIC ELECT'L CONTRG
Firm Phone: 212-219-3336  Firm Address: 137 CHRYSTIE STREET NEW YORK NY 10002 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $121.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JAMES HELLER
Owner Business Name: MARINE TOWERS ASSOCIATES
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  1-NO.2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  1-200 AMP PNL
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001                      75 
Buildings Total                        75 
Total Units : 75 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/13/2009 Notice: 1 - FIRST NOTICE 09/20/2013
Power Issued: 01/13/2009 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M288647
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/12/2013 09/20/2013 CLC V D (60) (7) Y
INSPECTION COMMENTS: *RESTAURANT NEW NAME IS PICK A BAGEL/TRANSFORMER FEEF FROM 2ND FL SPLICE BOX NOT ACCESSIBLE* **SEE OBJECTIONS
 
(2) 05/20/2014 05/29/2014 JSB C R E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M288647
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
1ST FL: GND HAS NOT BEEN PROVIDED FOR TRANSFORMER.. - 250.30A
RSLV 09/12/2013 09/12/2013 05/20/2014
 
002 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
1ST FL: TRANSFORMER PRIMARY CONDUCTORS NOT COLORED B O Y
RSLV 09/12/2013 09/12/2013 05/20/2014
 
003 ( 19) DEFECTIVE WIRING IS IN USE
1ST FL: 200 AMP PANEL PHASE CONDUCTOR BURNING
RSLV 09/12/2013 09/12/2013 05/20/2014
 
004 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
1ST FL: 200 AMP PANEL 12 WIRE FUSED AT 40 AMPS
RSLV 09/12/2013 09/12/2013 05/20/2014
 
005 (999) OTHER
1ST.FL: KITCHEN 100 AMP DISCONN NEUTRAL BOND 250.24A5
RSLV 09/12/2013 09/12/2013 05/20/2014
 
006 (999) OTHER
1ST FL: TRANSFORMER SECONDARY MORE THAN SIX DISCONN PROVIDED- 450.3A NOTE 2
RSLV 09/12/2013 09/12/2013 05/20/2014
 
007 (999) OTHER
1ST FL: TRANSFORMER DISCON WITHIN 25'...... - 240.21B2
RSLV 09/12/2013 09/12/2013 05/20/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back