BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M288618
Premises: 124 HUDSON STREET MANHATTAN BIN: 1002166     Block: 190   Lot: 7506
   
Application Completed and Certified

Filed: 124 HUDSON ST Census Tract:   33 Health Area:  7700
BASEMENT AND ROOF Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   101
DOB Cross Street(s):   NORTH MOORE STREET,    ERICSSON PLACE
Status:   C - JOB IS SIGNED OFF 11/04/2009
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/13/2009 11:54 AM
Application Entered:   01/13/2009 Job Start Date:   01/15/2009
Last Change:   11/04/2009 Job End Date:   03/10/2009
Appointment Status:   
Last Inspection By:   CHARLES COURTNEY       On     10/29/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010502 Licensee Name: RAYMOND T JOHNSON
Firm: 003361 Firm Name: ELMAC ELECTRIC INC.
Firm Phone: 718-894-9727  Firm Address: 97-77 QUEENS BLVD TOWER FLOOR REGO PARK NY 11374 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $100.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Other
Store / Other:   CELL SITE
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: METRO PCS
Authorized Representative:  JOHN MARINO
Relationship To Owner:   MANAGER OF CONSTRUCTION


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3 # 3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  20 CIRCUITS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                 
Buildings Total                 
Total Units : 4 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 09/18/2009
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALL 200A RISER FOR ROOF EQUIPMENT FOR MERO PCS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M288618
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/11/2009 09/18/2009 CCH A (30) (1) Y
INSPECTION COMMENTS: NO ACCESS
 
(2) 10/29/2009 11/04/2009 CCH C R (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M288618
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
STAIRWAY,ALL PULL BOXES & L.B. COVER WITH SHEET ROCK NO ACCESS,314.29
RSLV 09/11/2009 09/11/2009 10/29/2009



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order