BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M288581
Premises: 57 WEST 35 STREET MANHATTAN BIN: 1088537     Block: 837   Lot: 9
   
Application Completed and Certified

Filed: 59 W 35 ST Census Tract:   84 Health Area:  5200
1ST/BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   105
Related Job Number:    104507295
DOB Cross Street(s):    5 AVENUE,    AVENUE OF THE AMERICAS
Status:   C - JOB IS SIGNED OFF 11/23/2009
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/12/2009 12:38 PM
Application Entered:   01/12/2009 Job Start Date:   01/12/2009
Last Change:   11/23/2009 Job End Date:   01/16/2009
Appointment Status:   
Last Inspection By:   DORSAINVILLE, R       On     09/09/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012127 Licensee Name: LUIGI MARCELLINO
Firm: 003832 Firm Name: PRINCE ELEC'L CONTR'G COR
Firm Phone: 718-792-7292  Firm Address: 1140 BRONX RIVER AVENUE BRONX NY 10472 

Work Started or Filed by Others: YES
Work Category:   N - NEW BUILDING Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $45.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   H - Hotel
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval # / Submittal #:   07A0340
Owner / Occup: CARMINE DELLA CAVA
Owner Business Name: CAVA CONSTRUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    10  10    10             
Buildings Total 10  10    10                
Total Units : 33 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  03/26/2009
Power Issued: Response: W - OBJ TO BE REMOVED 04/09/2009

Follow-Up: K - (CLOSED)
Contractor's Comments:  COMPLETE WORK STARTED BY OTHER CONTRACTOR. ORIGINAL CONTRACTOR ( JOHN DONADIO DIED). PERMIT #M265690 ADVISORY BOARD # 07A0340.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M288581
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/17/2009 03/26/2009 JSB A (60) (4) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 09/09/2009 09/18/2009 RID C R (15) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M288581
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
ROOF: LSFP FEEDER FROM CONT NOT RIGID COND695.6B(2)
RSLV 03/17/2009 03/17/2009 09/09/2009
 
002 (999) OTHER
A) BSMT: SVC RM NO PANIC BAR PROVIDED110.26C.2
RSLV 03/17/2009 03/17/2009 09/09/2009
 
003 ( 29) OUTLET BOXES ARE NOT COVERED
20TH FLOOR: TAP BOX 20TH FLOOR ELECT CLOSET NO ACCESS
RSLV 03/17/2009 03/17/2009 09/09/2009
 
004 (999) OTHER
B) 20TH FLOOR: ACCESS DOOR ELECT NO 6 1/2' X 30"110.33
RSLV 03/17/2009 03/17/2009 09/09/2009



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.