Electrical Application Details for App #: M288064
Premises: 33 CLINTON STREET MANHATTAN BIN: 1004222     Block: 349   Lot: 19
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 33 CLINTON ST Census Tract:   30.01 Health Area:  6600
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10002 Community Board:   103
DOB Cross Street(s):   STANTON STREET,    RIVINGTON STREET
Status:   C - JOB IS SIGNED OFF 03/01/2016
Request Type:   P - PICK-UP eFiled:   YES
Application Entered:   02/18/2016 Job Start Date:   02/19/2016
Last Change:   03/01/2016 Job End Date:   02/24/2016
Appointment Status:   
Last Inspection By:   CONROY BLAKE       On     02/29/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009365 Licensee Name: MICHAEL SCHONDORF
Firm: 000995 Firm Name: MICHAEL SCHONDORF, INC
Firm Phone: 212-244-4312  Firm Address: 545 WEST 45TH STREET..6F NEW YORK NY 10036 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $40.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ----------- -------------
Owner Business Name: 37-39 CLINTON COURT
Authorized Representative:  JOYCE KWECNINSKI
Relationship To Owner:   BUILDING MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                   
Buildings Total                   
Total Units : 3 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  12/18/2008
Power Issued: Response: F - FILED TO REMOVE OBJECTION 02/18/2016

Follow-Up: X - FILED APPL,NOW CLOSED 02/18/2016
Contractor's Comments:  NEW GROUND CLAMP, NEW WIRE, NEW GROUND ROD, NEW GROUND BAR

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M288064
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/11/2008 12/18/2008 SR2 W (15) (3)
INSPECTION COMMENTS: NONE
 
(2) 02/29/2016 03/01/2016 CBK C R (40) (0)
INSPECTION COMMENTS: PASS.

OBJECTION FOR APPLICATION #: M288064
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
(ALL FLOORS)DEFECTIVE EXTREMELY CORODED CONN AT WATER PIPE,SERVICE GRD CONDUCTOR, NO METALLIC/METALLIC CONTINUITY CONTACT DUE TO CORRODED CONN AT WA
RSLV 12/11/2008 12/11/2008 02/29/2016
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(ALL FLOORS)DEFECTIVE EXTREMELY CORRODED CONN AT WATER PIPE, SERVICE GRD CONDUCTOR, NO METALLIC/METALLIC CONTINUITY CONTACT DUE TO CORRODED CONN AT
RSLV 12/11/2008 12/11/2008 02/29/2016
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS)NO NEUTRAL/ENCL BONDING 400A S/S EXIST AT MAIN SERVICE DISC SW FOR THE BLDG,NOT A FINAL INSPECTION, REF#M283208
RSLV 12/11/2008 12/11/2008 02/29/2016