BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M286798
Premises: 565 BROADWAY MANHATTAN BIN: 1007573     Block: 498   Lot: 5
   
Application Completed and Certified

Filed: 565 BROADWAY Census Tract:   49 Health Area:  6800
5E Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   SPRING STREET,    PRINCE STREET
Status:   C - JOB IS SIGNED OFF 06/12/2009
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/09/2008 3:48 PM
Application Entered:   11/09/2008 Job Start Date:   11/20/2008
Last Change:   06/12/2009 Job End Date:   05/15/2009
Appointment Status:   
Last Inspection By:   REDDINGTON, J.       On     06/02/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012015 Licensee Name: MIECZYSLAW KARDASZ
Firm: 003926 Firm Name: MK ELECTRIC CONTR'S, INC
Firm Phone: 718-646-0128  Firm Address: 10 BAY 22ND STREET BROOKLYN NY 11214 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $129.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Commercial/Residential (1  Stores, 14 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MATTHEW BOBE
Owner Business Name: KM ASSOCIATES OF NY, INC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  4#2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
005  5W  25  34    14  25     
Buildings Total 25  34    14  25            
Total Units : 108 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/09/2008 Notice:  04/28/2009
Power Issued: 11/09/2008 Response: V - OBJ WAS REMOVED 05/04/2009

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M286798
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/16/2009 04/28/2009 CCH A E (60) (5) Y
INSPECTION COMMENTS: SEE VIOLATION DETAILS
 
(2) 06/02/2009 06/12/2009 SR2 C R E (30) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M286798
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
DIN.ROOM: HANGING LIGHT FIXTURE NO GROUND410.17
RSLV 04/16/2009 04/16/2009 06/02/2009
 
002 ( 35) APPROVED OUTLETS HAVE NOT BEEN PROVIDED FOR AIR CONDITIONERS
LIV.ROOM: A/C WINDOW UNIT ON REG OUTLET CIR
RSLV 04/16/2009 04/16/2009 06/02/2009
 
003 (999) OTHER
BEDROOM: NO A/C OUTLET210.52(1)
RSLV 04/16/2009 04/16/2009 06/02/2009
 
004 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
BEDROOM: CLOSET LIGHT NO SHADE
RSLV 04/16/2009 04/16/2009 06/02/2009
 
005 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
PANEL: KO MISSING
RSLV 04/16/2009 04/16/2009 06/02/2009



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back